product_specification:pws2-30k-na

This is an old revision of the document!


PWS2-30K-NA

Item Heading 3
Row 1 Col 1 Row 1 Col 2
Row 2 Col 1 some colspan
Row 3 Col 1 Row 3 Col 2
Utility-interactive Mode
Battery charge/discharge voltage200V~750V (350~750V Full Power)
Battery charge/discharge current90A Max
AC voltage480V(423V~528V)
AC current36A
Nominal power30kW
AC frequency
AC PFListed: 0.8~1 leading or lagging (Controllable)
Actual: 0.1~1 leading or lagging (Controllable)
Stand-alone Mode
Battery discharge voltage
Battery discharge current
AC output voltage480V(±5% configurable)
AC output current
Nominal AC output power30kW(33kW max)
AC frequency60Hz
AC output PFListed: 0.8~1 leading or lagging (Load-depend)
Actual: 0.1~1 leading or lagging (Load-depend)
Overload Capability105%~115% 10min;
115%~125% 1min;
125%~150% 200ms
Physical
CoolingForced air cooling with replaceable fan module
Noise <65dB
EnclosureIP32/NEMA1
Max elevation3000m/10000feet (> 2000m/6500feet derating)
Operating temperature-20°C to 60°C (De-rating over 45°C)
Humidity0~95% (No condensing)
Size (W*H*D)470*660*176mm
Weight43kg
InstallationWall-mounted
Other
Peak efficiency97.3%
CEC efficiency96.5%
Protection
AC connection 3-Phase+N+PE /240V Split-phase (extra transformer required, derated to 17.3kW)
IsolationNon-isolation
CertificationETL listed conforming to UL1741/UL1741SA, CPUC RULE 21, IEEE1547
Short circuit
Peak short circuit current62A@20ms
Initial value of aperiodic current62A@100ms
Initial symmetrical short circuit current54A@250ms
Decaying component of short circuit current54A@500ms
Time to trip119ms
  • product_specification/pws2-30k-na.1545814121.txt.gz
  • Last modified: 2020/09/16 21:01