Specifications of PWS1-50K-NA / PWS1-100K-NA / PWS1-150K-NA / PWS1-250K-NA

ModelPWS1-50K-NAPWS1-100K-NAPWS1-150K-NAPWS1-250K-NA
Utility-interactive Mode
Battery dis-/charge voltage 500V~850V
Battery dis-/charge current 0~110A 0~220A 0~330A 0~550A
AC voltage 480V(423V~528V)
AC current 60A 120A 180A 300A
Nominal power 50kVA 100kVA 150kVA 250kVA
AC frequency 60Hz (59.5Hz~60.5Hz)
AC PF Listed: 0.8~1 leading or lagging (Controllable)
Actual: 0.1~1 leading or lagging (Controllable)
Stand-alone Mode
Battery discharge voltage 500V~850V
Battery discharge current 0~110A 0~220A 0~330A 0~550A
AC output voltage 480V (±5% configurable)
AC output current 60A 120A 180A 300A
Nominal AC output power 50kVA (55kVA max)
AC frequency 60Hz
AC output PF Listed: 0.8~1 leading or lagging (Load-depend)
Actual: 0.1~1 leading or lagging (Load-depend)
Overload Capability 105%~115% 10min;
115%~125% 1min;
125%~150% 200ms
Physical
Cooling Forced air cooling
Noise <65dB
Enclosure IP20/NEMA1
Max elevation 3000m/10000feet (> 2000m/6500feet derating)
Operating temperature -20°C to 60°C (De-rating over 45°C)
Humidity 0~95% (No condensing)
Size (W*H*D) 800*2160*800mm 1200*2160*800mm
Weight 465kg
Installation Floor standing
Other
Peak efficiency 95.5%
CEC efficiency 94%
Protection Over temperature,
AC over/under current,
AC over/under frequency,
EPO,
AC phase reversion,
Fan/relay failure,
Over load,
GFDI(AC),
Anti-islanding,
Configurable protection limits: Upper/lower AC voltage/frequency limit, battery EOD voltage.
AC connection 3-Phase 4-wire
Isolation internal transformer
Certification ETL listed conforming to UL1741/UL1741SA, CPUC Rule 21, HECO Rule 14H, IEEE1547, HECO listed, CA listed
Short circuit
Short circuit current 200A 400A 600A 1000A
Time to trip 100ms