Specifications of PWS1-50K-NA / PWS1-100K-NA / PWS1-150K-NA / PWS1-250K-NA
Model | PWS1-50K-NA | PWS1-100K-NA | PWS1-150K-NA | PWS1-250K-NA |
---|---|---|---|---|
Utility-interactive Mode | ||||
Battery dis-/charge voltage | 500V~850V | |||
Battery dis-/charge current | 0~110A | 0~220A | 0~330A | 0~550A |
AC voltage | 480V(423V~528V) | |||
AC current | 60A | 120A | 180A | 300A |
Nominal power | 50kVA | 100kVA | 150kVA | 250kVA |
AC frequency | 60Hz(59.5Hz~60.5Hz) | |||
AC PF | Listed: 0.8~1 leading or lagging (Controllable) Actual: 0.1~1 leading or lagging (Controllable) |
|||
Stand-alone Mode | ||||
Battery discharge voltage | 500V~850V | |||
Battery discharge current | 0~110A | 0~220A | 0~330A | 0~550A |
AC output voltage | 480V(±5% configurable) | |||
AC output current | 60A | 120A | 180A | 300A |
Nominal AC output power | 50kVA (55kVA max) | |||
AC frequency | 60Hz | |||
AC output PF | Listed: 0.8~1 leading or lagging (Load-depend) Actual: 0.1~1 leading or lagging (Load-depend) |
|||
Overload Capability | 105%~115% 10min; 115%~125% 1min; 125%~150% 200ms |
|||
Physical | ||||
Cooling | Forced air cooling | |||
Noise | <65dB | |||
Enclosure | IP20/NEMA1 | |||
Max elevation | 3000m/10000feet (> 2000m/6500feet derating) | |||
Operating temperature | -20°C to 60°C (De-rating over 45°C) | |||
Humidity | 0~95% (No condensing) | |||
Size (W*H*D) | 800*2160*800mm | 1200*2160*800mm | ||
Weight | 465kg | |||
Installation | Floor standing | |||
Other | ||||
Peak efficiency | 95.5% | |||
CEC efficiency | 94% | |||
Protection | Over temperature, AC over/under current, AC over/under frequency, EPO, AC phase reversion, Fan/relay failure, Over load, GFDI(AC), Anti-islanding, Configurable protection limits: Upper/lower AC voltage/frequency limit, battery EOD voltage. |
|||
AC connection | 3-Phase 4-wire | |||
Isolation | internal transformer | |||
Certification | ETL listed conforming to UL1741/UL1741SA, CPUC Rule 21, HECO Rule 14H, IEEE1547, HECO listed, CA listed | |||
Short circuit | ||||
Short circuit current | 200A | 400A | 600A | 1000A |
Time to trip | 100ms |