manual:pws2-30k:status_and_fault_list

Status and Fault List

AddressBitFlagFlag categoryFlag name in ChineseValue
32Bit0 Fault statusFault故障: 故障综合0: False; 1:ture
32Bit1 Alert statusWarning告警: 告警综合0: False; 1:ture
32Bit2 On/Off statusStatus状态: 已开机0: False; 1:ture
32Bit3 On-gridStatus状态: 并网0: False; 1:ture
32Bit4 Off-grid(Island mode)Status状态: 离网0: False; 1:ture
32Bit5 Reserved
32Bit6 Reserved
32Bit7 Reserved
32Bit8-15 Reserved
33Bit0-7 Reserved
33Bit8 anti-islanding function enabledStatus状态: 孤岛保护使能0: False; 1:ture
33Bit9-15 Reserved
34Bit0-7 Reserved
34Bit8-15 Reserved
35Bit0-7 Reserved
35Bit8-15 Reserved
36bit0 AC OVPWarning告警: 交流侧过压保护0: False; 1:ture
36Bit1 AC UVPWarning告警: 交流侧欠压保护0: False; 1:ture
36Bit2 AC OFPWarning告警: 交流侧过频保护0: False; 1:ture
36Bit3 AC UFPWarning告警: 交流侧欠频保护0: False; 1:ture
36Bit4 Grid voltage unbalance. Warning告警: 电网电压不平衡0: False; 1:ture
36Bit5 Grid phase reverseWarning告警: 电网电压反序0: False; 1:ture
36Bit6 Anti-islanding scheme taking effect (and grid is out)Status状态: 孤岛状态0: False; 1:ture
36Bit7 On/off-grid switching errorWarning告警: 并离网切换故障0: False; 1:ture
36Bit8 Output grounding errorFault故障: 输出接地故障0: False; 1:ture
36Bit9 Reserved
36Bit10 Grid phase lock failedWarning告警: 电网锁相失败0: False; 1:ture
36Bit11 Internal air over-tempWarning告警: 内部环境温度过温0: False; 1:ture
36Bit12 Enabling grid-tieing criterion detecting timeoutStatus状态: 并网条件判断超时使能0: False; 1:ture
36Bit13-15 Reserved
37Bit0 EPO(Emergency Power-off) trippingWarning告警: 急停按钮被按下0: False; 1:ture
37bit1 HMI parameters faultFault故障: 监控参数故障0: False; 1:ture
37Bit2 DSP version errorFault故障: DSP软件版本错误0: False; 1:ture
37Bit3 CPLD version errorFault故障: CPLD软件版本错误0: False; 1:ture
37Bit4 Hardware Version errorFault故障: 硬件版本错误0: False; 1:ture
37Bit5 Communication errorFault故障: 通讯错误0: False; 1:ture
37Bit6 Aux power errorFault故障: 辅助电源错误0: False; 1:ture
37Bit7 Fan failureFault故障: 风扇故障0: False; 1:ture
37Bit8 BUS over voltageWarning告警: 母线电压过压0: False; 1:ture
37Bit9 BUS low voltageWarning告警: 母线电压欠压0: False; 1:ture
37Bit10 BUS voltage unbanlacedWarning告警: 母线电压不平衡0: False; 1:ture
37Bit11 Reserved
37Bit12 Reserved
37Bit13 Output voltage abnormal.Fault故障: 输出电压异常0: False; 1:ture
37Bit14 Output current unbalancedFault故障: 输出电流不平衡0: False; 1:ture
37Bit15 Over-temperature of heat sinkWarning告警: 散热器过温0: False; 1:ture
38Bit0 Output OverloadWarning告警: 输出过载0: False; 1:ture
38Bit1 Reserved0: False; 1:ture
38Bit2 AC relay short-circuit.Fault故障: AC继电器短路0: False; 1:ture
38Bit3 Inverter start failure. Fault故障: 逆变器启动失败0: False; 1:ture
38Bit4 AC relay is open. Fault故障: AC继电器开路0: False; 1:ture
38Bit5-15 Reserved0: False; 1:ture
39Bit0 EE Reading error 1Fault故障: EE读取错误10: False; 1:ture
39Bit1 EE Reading error 2Fault故障: EE读取错误20: False; 1:ture
39Bit2 Reserved
39Bit3 Inverter over loadWarning告警: 逆变器过载0: False; 1:ture
39Bit4-15 Reserved
40bit0 DC chargingStatus状态: DC充电中0: False; 1:ture
40bit1 DC dischargingStatus状态: DC放电中0: False; 1:ture
40bit2 Battery fully chargedStatus状态: 电池充满0: False; 1:ture
40bit3 Battery emptyStatus状态: 电池放空0: False; 1:ture
40Bit4 Reserved
40Bit5 Reserved
40Bit6-15 Reserved
41Bit0-7 Reserved
41Bit8-15 Reserved
42Bit0-7 Reserved
42Bit8-15 Reserved
43Bit0-7 Reserved
43Bit8-15 Reserved
44Bit0 DC input OVP(over voltage protection)Warning告警: DC输入过压保护0: False; 1:ture
44Bit1 DC input UVP(under voltage protection)Warning告警: DC输入欠压保护0: False; 1:ture
44Bit2 Reserved
44Bit3 BMS Alerts.(available only BMS connected)Warning告警: BMS告警0: False; 1:ture
44Bit4-7 Reserved0: False; 1:ture
44Bit8-15 Reserved0: False; 1:ture
45bit0 DC soft-start failed. Warning告警: DC软起动失败0: False; 1:ture
45bit1 DC relay short-circuit.Fault故障: DC继电器短路0: False; 1:ture
45bit2 DC relay short-openFault故障: DC继电器开路0: False; 1:ture
45Bit3 Battery power over load.0: False; 1:ture
45Bit4 DC BUS starting failedWarning告警: 母线启动失败0: False; 1:ture
45Bit5-7 Reserved
45Bit8-15 Reserved
46Bit0-7 Reserved
46Bit8-15 Reserved
47Bit0 DC OCPWarning告警: DC过流保护0: False; 1:ture
47Bit1-7 Reserved
47Bit8-15 Reserved
48-63 Reserved