Droop mode precautions

  • Since firmware D141, droop mode has been added to PWS2-30K/M, to provide a non-communication off-grid parallel operation solution.
  • Only 3-phase PWS2-30K/M supports droop mode, single phase firmware does NOT support droop mode yet.
  • To write register 0x02EE and 0x02F4, authorization must be granted first, by writing 2007 to 0x0FA7 and 2016 to 0x0FA8.
  • The PWS2-30K must be set to 3P3W, 0x02EE=1; and NO neutral line connected
  • To enable droop mode, set 0x02F4=1
  • After enabling droop mode, a hard reboot is required.
  • A delta-wye transformer is required if 277V or 220V single phase load is required.
  • When multiple PWS2-30K/M are used for off-grid droop parallel operation, there must be one PWS2-30K establishing AC voltage first, and then the others can be started.
  • The maximum quantity of PWS2-30K/M for off-grid droop parallel operation in one microgrid is 9
  • When droop parallel operation implemented, the length of the cables from the PWS2-30K/M should be as same as possible.
  • The droop mode will bring voltage and frequency fluctuation (90%~110%)
  • The droop mode will bring some circulating current between each PWS2-30K/M, if the load is low in off-grid microgrid, the currents of each DC side of the PWS2-30K will be fluctuating not more than of ±5%
  • If droop mode is enabled in grid-tied mode, there will be some unpredictable reactive power, DISABLE droop mode if it's not necessary for the grid-tied operaion.