Communication protocol

This protocol supports MODBUS TCP/IP or MODBUS RTU

Function codes supported: 03 reading, 06 writing.

AdressStartEndSizeAccessRegister NameRegister Name in ChineseTypeUnitCommentsMagnificationRange(real value)Default(real value)Remark
0x000111616Rmodel String(32) Manufacturer and model number
0x001117248Rserial String(16) Serial Number
0x002032321Rfault_occurred_0 uint16x Faults 15:0 occured refer to Status and fault list
0x002133331Rfault_occurred_1 uint16x Faults 31:16 occured refer to Status and fault list
0x002234341Rfault_occurred_2 uint16x Faults 47:32 occured refer to Status and fault list
0x002335351Rfault_occurred_3 uint16x Faults 63:48 occured refer to Status and fault list
0x002436361Rfault_occurred_4 uint16x Faults 79:64 occured refer to Status and fault list
0x002537371Rfault_occurred_5 uint16x Faults 95:80 occured refer to Status and fault list
0x002638381Rfault_occurred_6 uint16x Faults 111:96 occured refer to Status and fault list
0x002739391Rfault_occurred_7 uint16x Faults 127:112 occurred refer to Status and fault list
0x002840401Rfault_occurred_8 uint16x Faults 143:128 occurred refer to Status and fault list
0x002941411Rfault_occurred_9 uint16x Faults 159:144 occured refer to Status and fault list
0x002A42421Rfault_occurred_10 uint16x Faults 175:160 occured refer to Status and fault list
0x002B43431Rfault_occurred_11 uint16x Faults 191:176 occured refer to Status and fault list
0x002C44441Rfault_occurred_12 uint16x Faults 207:192 occured refer to Status and fault list
0x002D45451Rfault_occurred_13 uint16x Faults 223:208 occured refer to Status and fault list
0x002E46461Rfault_occurred_14 uint16x Faults 239:224 occured refer to Status and fault list
0x002F47471Rfault_occurred_15 uint16x Faults 255:240 occurred refer to Status and fault list
0x003048481Rfault_occurred_16 uint16x Faults 271:256 occured refer to Status and fault list
0x003149491Rfault_occurred_17 uint16x Faults 287:272 occured refer to Status and fault list
0x003250501Rfault_occurred_18 uint16x Faults 303:288 occured refer to Status and fault list
0x003351511Rfault_occurred_19 uint16x Faults 319:304 occured refer to Status and fault list
0x003452521Rfault_occurred_20 uint16x Faults 335:320 occured refer to Status and fault list
0x003553531Rfault_occurred_21 uint16x Faults 351:336 occured refer to Status and fault list
0x003654541Rfault_occurred_22 uint16x Faults 367:352 occured refer to Status and fault list
0x003755551Rfault_occurred_23 uint16x Faults 383:368 occurred refer to Status and fault list
0x003856561Rfault_occurred_24 uint16x Faults 399:384 occured refer to Status and fault list
0x003957571Rfault_occurred_25 uint16x Faults 415:400 occured refer to Status and fault list
0x003A58581Rfault_occurred_26 uint16x Faults 431:416 occured refer to Status and fault list
0x003B59591Rfault_occurred_27 uint16x Faults 447:432 occured refer to Status and fault list
0x003C60601Rfault_occurred_28 uint16x Faults 463:448 occured refer to Status and fault list
0x003D61611Rfault_occurred_29 uint16x Faults 479:464 occured refer to Status and fault list
0x003E62621Rfault_occurred_30 uint16x Faults 495:480 occured refer to Status and fault list
0x003F63631Rfault_occurred_31 uint16x Faults 512:496 occurred refer to Status and fault list
0x00651011011RInvOutVolt_A _Rms_Value模块端口AB线电压(*10)int16VAC A-B RMS voltage×10 Indicates the A-B RMS voltage
0x00661021021RInvOutVolt_B _Rms_Value模块端口BC线电压(*10)int16VAC B-C RMS voltage×10 Indicates the B-C RMS voltage
0x00671031031RInvOutVolt_C_Rms_value模块端口CA线电压(*10)int16VAC C-A RMS voltage×10 Indicates the C-A RMS voltage
0x00681041041RAnalog_A_GridCurrent_Rms_ValueA相输出电流(*10)int16AAC phA RMS current×10 Indicates the output current of Phase A
0x00691051051RAnalog_B_GridCurrent_Rms_ValueB相输出电流(*10)int16AAC phB RMS current×10 Indicates the output current of Phase B
0x006A1061061RAnalog_C_GridCurrent_Rms_ValueC相输出电流(*10)int16AAC phC RMS current×10 Indicates the output current of Phase C
0x006B1071071RAnalog_GridCurrent_Freq电网频率(*100)int16HzAC frequency×100 Indicates the frequency of the grid
0x006E1101101RAnalog_A_ActivePower_Rms_ValueA相有功功率(*100)int16kWAC phA Active Power×100 Indicates the active power of Phase A
0x006F1111111RAnalog_B_ActivePower_Rms_ValueB相有功功率(*100)int16kWAC phB Active Power×100 Indicates the active power of Phase B
0x00701121121RAnalog_C_ActivePower_Rms_ValueC相有功功率(*100)int16kWAC phC Active Power×100 Indicates the active power of Phase C
0x00711131131RAnalog_A_ReactivePower_Rms_ValueA相无功功率(*100)int16kVARAC phA Reactive Power×100 Indicates the reactive power of Phase A
0x00721141141RAnalog_B_ReactivePower_Rms_ValueB相无功功率(*100)int16kVARAC phB Reactive Power×100 Indicates the reactive power of Phase B
0x00731151151RAnalog_C_ReactivePower_Rms_ValueC相无功功率(*100)int16kVARAC phC Reactive Power×100 Indicates the reactive power of Phase C
0x00741161161RAnalog_A_ApparentPowerA相视在功率(*100)int16kVAAC phA Apparent Power×100 Indicates the apparent power of Phase A
0x00751171171RAnalog_B_ApparentPowerB相视在功率(*100)int16kVAAC phB Apparent Power×100 Indicates the apparent power of Phase B
0x00761181181RAnalog_C_ApparentPowerC相视在功率(*100)int16kVAAC phC Apparent Power×100 Indicates the apparent power of Phase C
0x00771191191RAnalog_A_PF_Rms_ValueA相功率因数(*100)int16PFAC phA Power Factor×100 Indicates the power factor of Phase A
0x00781201201RAnalog_B_PF_Rms_ValueB相功率因数(*100)int16PFAC phB Power Factor×100 Indicates the power factor of Phase B
0x00791211211RAnalog_C_PF_Rms_ValueC相功率因数(*100)int16PFAC phC Power Factor×100 Indicates the power factor of Phase C
0x007A1221221RAnalog_ ActivePower_3Phase三相总有功功率(*100)int16kWAC Real Power×100 Indicates the active power of the inverter
0x007B1231231RAnalog_ ReactivePower_3Phase三相总无功功率(*100)int16kVARAC Reactive Power×100 Indicates the reactive power of the inverter
0x007C1241241RAnalog_ ApparentPower_3Phase三相总视在功率(*100)int16kVAAC Apparent Power×100 Indicates the apparent power of the inverter
0x007D1251251RAnalog_ PowerFactor_3Phase三相总PF值int16 AC Power Factor×100 Indicates the general power factor of the inverter
0x007E1261272RWAnalog_Dischg_Energy馈网电量(*10)uint32kWh ×10 '0' value can be written to the register to reset their value
0x00801281292RWAnalog_Chg_Energy电网供电电量(*10)uint32kWh ×10 '0' value can be written to the register to reset their value
0x00821301312RAnalog_Reactive_Energy无功电量(*10)uint32kWhReactive energy×10 useless in most cases
0x00841321321RTemperature_Of_AC_ Heat_SinkDCAC散热器温度(*1)int16CTemperature of AC heat sink×1
0x00851331331RPositive_BUS_Voltage正母线电压*10int16VBUS+ side voltage×10
0x00861341341RNegtive_BUS_Voltage负母线电压*10int16VBUS- side voltage×10
0x00871351351RWTarget_Active_Power有功功率期望int16kWTarget active power×10 -30.0kW ~30.0kW0minus: charge
positive: discharge
e.g.:10kW write+100 to the inverter
0x00881361361RWTarget_Reactive_Power无功功率期望int16kVARTarget reactive power×10-30.0kVAr~30.0kVAr0minus: inductive
positive: capacitive
0x00891371371RWTarget_Off-grid_Voltage离网电压期望int16VTarget off-grid voltage bias×100-0.10~0.10(to rated voltage)0Available only in off-gird mode
0x008A1381381RWTarget_Off-grid_Frequency离网频率期望int16HzTarget off-grid frequency bias×100-2.0~2.0Hz0Available only in off-gird mode
0x008D1411411RAnalog_DC_Power直流功率(*100)int16kWDC power×100
0x008E1421421RAnalog_DC_Voltage直流电压(*10)int16VDC voltage×10
0x008F1431431RAnalog_DC_Current直流电流(*10)int16ADC current×10
0x00901441452RWAnalog_DC_Chg_Energy直流充电电量(*1)uint32kWhDC charged energy×1 '0' value can be written to the register to reset their value
0x00921461472RWAnalog_ DC_Dischg_Energy直流放电电量(*1)uint32kWhDC discharged energy×1 '0' value can be written to the register to reset their value
0x00941481481RTemperature_Of_DCDC_Heat_SinkDCDC散热器温度(*1)int16CTemperature of DC heat sink×1 Indicates the
0x00A81681681RD.C._Voltage直流电压uint16VD.C. Voltage BMS protocol for Vendor B
Vendor B protocol is only for transferring the data from BMS via RS485 to EMS via Ethernet, no protection will be applied by inverter.
Vendor A protocol provides protection and status display by inverter
0x00A91691691RD.C._Voltage_SFSF=Scale factor,下设倍率sunssfSFD.C. Voltage SF BMS protocol for Vendor B
0x00AA1701701RD.C._Current直流电流uint16AD.C. Current BMS protocol for Vendor B
0x00AB1711711RD.C._Current_SFSF=Scale factor,下设倍率sunssfSFD.C. Current SF BMS protocol for Vendor B
0x00AC1721721Raverage_temp平均温度uint16Caverage temp BMS protocol for Vendor B
0x00AD1731731Raverage_temp_SFSF=Scale factor,下设倍率sunssfSFaverage temp SF BMS protocol for Vendor B
0x00AE1741741Rmax_temp最大温度uint16Cmax temp BMS protocol for Vendor B
0x00AF1751751Rmax_temp_SFSF=Scale factor,下设倍率sunssfSFmax temp SF BMS protocol for Vendor B
0x00B01761761Rmin_Temp最小温度uint16Cmin Temp BMS protocol for Vendor B
0x00B11771771Rmin_Temp_SFSF=Scale factor,下设倍率sunssfSFmin Temp SF BMS protocol for Vendor B
0x00B21781781Rmax_cell_volt最大电池电压uint16Vmax cell volt BMS protocol for Vendor B
0x00B31791791Rmax_cell_volt_SFSF=Scale factor,下设倍率sunssfSFmax cell volt SF BMS protocol for Vendor B
0x00B41801801Rmin_cell_volt最小电池电压uint16Vmin cell volt BMS protocol for Vendor B
0x00B51811811Rmin_cell_volt_SFSF=Scale factor,下设倍率sunssfSFmin cell volt SF BMS protocol for Vendor B
0x00B61821821Raverage_cell_volt平均电池电压uint16Vaverage cell volt BMS protocol for Vendor B
0x00B71831831Raverage_cell_volt_SFSF=Scale factor,下设倍率sunssfSFaverage cell volt SF BMS protocol for Vendor B
0x00B81841841Rsoc电池已充电容量与电池额定容量的比值uint16 SOC BMS protocol for Vendor B
0x00B91851851Rsoc_SFSF=Scale factor,下设倍率sunssfSFsoc SF BMS protocol for Vendor B
0x00BA1861861Rsoh电池可放出容量与新电池额定容量的比值uint16 SOC BMS protocol for Vendor B
0x00BB1871871Rsoh_SFSF=Scale factor,下设倍率sunssfSFsoh SF BMS protocol for Vendor B
0x012C3003034RWIP_AddressIP地址uint64 IP addreess take effect after hard reset, set on the HMI
Default IP 192.168.0.10, node ID 1
0x01303043074RWNetmask网络掩码uint64 Netmask take effect after hard reset
0x01343083114RWGateway网关IP地址uint64 Gateway IP address take effect after hard reset
0x01383123143RWMACMAC地址固定前两个字节00-24,后四个字节可修改uint48 MAC address first 2 bytes fixed as 00-24 the following 4 bytes is changeable, takes effect after hard reset
0x013C3163161RWModbus_Device_AddressModbus设备地址uint16 Modbus device address 1~2471take effect after hard reset
0x01403203201RWbaud_Rate接口波特率,单位为位/秒enum16 Interface baud rate in bits per second 0: 19200
1: 9600
0take effect after hard reset
0x01453253251RWInterface Type接口类型enum16 EMS Interface type 0: RS-485
1: Ethernet
0if implement RS-485 as EMS interface. BMS access is invalid TCP and RS485 can be used,TCP is recommended
0x01463263261RWProtocol_Selection串行协议选择 0-modbus 1-sunspec;默认1enum16 Serial protocol selection 0: modbus
1: sunspec
1should not be changed after 2017 old protocol is not used in the new products some redundant registers are both in the sunspec section and other sections.
0x01473273271RWEMS timeout settingEMS超时时间uint16s0=disabled×10~327670Prevent unexpected results of communication failures.when EMS timeout enabled, watchdog will work and even reading will feed the watchdog
0x01483283281RWEPO enable/disableEPO使能enum16 EPO enableing 0: disabled
1: enabled
0Enable ONLY when remote Emergency Stop Button is needed
0x01493293291RWBMS timeout settingBMS超时时间uint16s0=disabled×10~327670Enable ONLY when remote BMS-inverter connection is needed
SUNSPEC/MESA SECTION- START
0x01F45005012RSunSpec_ID知名价值。唯一标识这是一个SunSpec Modbus mapuint32x Well-known value. Uniquely identifies this as a SunSpec Modbus Map
0x01F65025021RSunSpec_DID_0001唯一标识这是一个SunSpec公共模型块uint16 Uniquely identifies this as a SunSpec Common Model Block
0x01F75035031RSunSpec_Length_000116位寄存器中的块长度uint16 Length of block in 16-bit registers
0x01F850451916RManufacturer string Manufacturer
0x020852053516RModel制造商特定值(32个字符)string Manufacturer specific value (32 chars)
0x02185365438ROptions制造商特定值(16个字符)string Manufacturer specific value (16 chars) 波特率+数据位+停止位+校验位
0x02205445518RVersion制造商特定值(16 chars)string Manufacturer specific value (16 chars)
0x022855256716RSerial Number制造商特定值(32个字符)string Manufacturer specific value (32 chars)
0x02385685681RWDevice AddressModbus设备地址uint16 Modbus device address
0x02395695691Rpad强制均匀对齐pad Force even alignment
0x023A5705701RSunSpec_DID_0103103 - 三相逆变器uint16 103 - 3-phase inverter
0x023B5715711RSunSpec_Length_0103模型块在寄存器中的长度uint16 Length of model block in registers
0x023C5725721RAmps交流电流uint16AAC Current
0x023D5735731RAmps PhaseAA相电流uint16APhase A Current
0x023E5745741RAmps PhaseBB相电流uint16APhase B Current
0x023F5755751RAmps PhaseCC相电流uint16APhase C Current
0x02405765761RA_SF交流电流??比例系数sunssfSFAC Current Scale factor
0x02415775771RPPVphABAB线电压uint16VPhase Voltage AB
0x02425785781RPPVphBCBC线电压uint16VPhase Voltage BC
0x02435795791RPPVphCACA线电压uint16VPhase Voltage CA
0x02445805801RPhVphAA相电压uint16VPhase Voltage AN
0x02455815811RPhVphBB相电压uint16VPhase Voltage BN
0x02465825821RPhVphCC相电压uint16VPhase Voltage CN
0x02475835831RV_SF交流电压比例系数sunssfSFAC Voltage Scale factor
0x02485845841RWatts交流功率int16WAC Power
0x02495855851RW_SF交流功率比例系数sunssfSFAC Power Scale factor
0x024A5865861RHz线路频率uint16HzLine Frequency
0x024B5875871RHz_SF比例系数sunssfSFScale factor
0x024C5885881RVA交流视在功率int16VAAC Apparent Power
0x024D5895891RVA_SF比例系数sunssfSFScale factor
0x024E5905901RVar交流无功功率int16varAC Reactive Power
0x024F5915911RVAr_SF比例系数sunssfSFScale factor
0x02505925921RPF交流功率因数int16PctAC Power Factor
0x02515935931RPF_SF比例系数sunssfSFScale factor
0x02525945952RWattHours交流能量acc32WhAC Energy
0x02545965961RWH_SF比例系数sunssfSFScale factor
0x02555975971RDC Amps直流电流uint16ADC Current
0x02565985981RDCA_SF比例系数sunssfSFScale factor
0x02575995991RDC Voltage直流电压uint16VDC Voltage
0x02586006001RDCV_SF比例系数sunssfSFScale factor
0x02596016011RDC Watts直流功率(*100)int16WDC Power×100
0x025A6026021RDCW_SF比例系数sunssfSFScale factor
0x025B6036031RCabinet Temperature机柜温度int16CCabinet Temperature
0x025C6046041RHeat Sink Temperature散热器温度int16CHeat Sink Temperature DCAC circuit heat sink
0x025D6056051RTransformer Temperature变压器温度int16CTransformer Temperature No transformer
0x025E6066061ROther Temperature其他温度int16COther Temperature DCDC circuit heat sink
0x025F6076071RTmp_SF温度比例系数sunssf Scale factor
0x02606086081ROperating State枚举值。工作状态enum16 Enumerated value. Operating state report the current operating status of the inverter
0x02616096091RVendor Operating State操作状态代码enum16 Vendor specific operating state code
0x02626106112REvent1位阈事件bitfield32 Bitmask value. Event fields
0x02646126132REvent Bitfield 2Faults 95:64 occuredbitfield32 Vendor defined events Faults 95:64 occured
0x02666146152RVendor Event Bitfield 1Faults 127:96 occuredbitfield32 Vendor defined events Faults 127:96 occured
0x02686166172RVendor Event Bitfield 2Faults 159:128 occurredbitfield32 Vendor defined events Faults 159:128 occurred
0x026A6186192RVendor Event Bitfield 3Faults 191:160 occuredbitfield32 Vendor defined events Faults 191:160 occured
0x026C6206212RVendor Event Bitfield 4Faults 223:192 occuredbitfield32 Vendor defined events Faults 223:192 occured
0x026E6226221RSunSpec_DID_FFFFSunSpec终止块uint16 SunSpec End Block
0x026F6236231RSunSpec_Length_FFFF结束块的长度uint16 Length of End Block
SUNSPEC/MESA SECTION- END
0x028A6506501RWSETDATA_ModOnCmd开机enum16 1: true
other: illegal
To Start operation, only 1 will be accepted. Reading back value makes no sense
0x028B6516511RWSETDATA_ModOffCmd关机enum16 1: true
other: illegal
To Stop operation, only 1 will be accepted. Reading back value makes no sense
0x028C6526521RWSETDATA_ClearFailureCmd清除故障enum16 Clearing fault 1: true
other: illegal
clear failure flag, when fault occurs, the system will stop and indicates fault.
starting is invalid until the fault source is actually removed and this register is written 1. Reading back value makes no sense
0x028D6536531RWSETDATA_OnGridCmd并网enum16 grid mode 1: true
other: illegal
set the module to on grid mode. Reading back value makes no sense
0x028E6546541RWSETDATA_OffGridCmd离网enum16 off grid mode 1: true
other: illegal
set the module to off grid mode. Reading back value makes no sense
0x028F6556551RWSETDATA_StandbyCmd待机enum16 standby(idle) mode 1: true
other: illegal
set the module to standby mode
setpoint 0:IGBT switching
setpoint 1:no IGBT switching, low consumption mode.let the inverter to halt the IGBT switching to save the power consumption, but all relays are still closed. Reading back value makes no sense
0x02EC7487481ROutput voltage输出电压等级enum16 Output voltage level 0: 380V
1: 400V
2: 480V
0Internal function, shall not be changed as will
0x02ED7497491ROutput frequency输出频率等级:50Hz/60Hzenum16 Output frequency level: 50 Hz / 60 Hz 0: 50Hz
1 60Hz
0Internal function, shall not be changed as will
0x02EE7507501RGrid type输出电压体制:三相四线制/三相三线制 enum16 Output voltage system: Three-phase four-wire / three-phase three-wire system 0: 3P4W
1: 3P3W or 3P3W+N
2Internal function, shall not be changed as will
0x02F17537531Routput power Rating模块功率等级:10kW/20kW/30kWenum16 Module power: 10 kW / 20 kW / 30 kW 0: 10kW
1: 20kW
2: 30kW
3: 29kW
Internal function, shall not be changed as will
0x02F27547541RDC voltage level 750/830未启用enum16 Not Implemented yet undefined0Internal function, shall not be changed as will
0x03007687681RWac_ov_trip_level_1电网过压I段保护幅值(IEEE1547)int16%Vratedratio×1001.05~1.21.1
0x03017697691RWac_ov_trip_time_1电网过压I段保护时间 (IEEE1547)int16s ×1000~13s1
0x03027707701RWac_ov_trip_level_2电网过压Ⅱ段保护幅值(IEEE1547)int16%Vratedratio×1001.05~1.21.1
0x03037717711RWac_ov_trip_time_2电网过压Ⅱ段保护时间 (IEEE1547)int16s ×1000~0.16s0.16
0x03047727721RWac_uv_trip_level_1电网欠压I段保护幅值(IEEE1547)int16%Vratedratio×1000. 45~0.950.88
0x03057737731RWac_uv_trip_time_1电网欠压I段保护时间 (IEEE1547)int16s ×1000~21s2
0x03067747741RWac_uv_trip_level_2电网欠压Ⅱ段保护幅值(IEEE1547)int16%Vratedratio×1000. 45~0.950.6
0x03077757751RWac_uv_trip_time_2电网欠压Ⅱ段保护时间 (IEEE1547)int16s ×1000~11s1
0x03087767761RWac_uv_trip_level_3电网欠压Ⅲ段保护幅值(IEEE1547)int16%Vratedratio×1000.45~0.950.45
0x03097777771RWac_uv_trip_time_3电网欠压Ⅲ段保护时间 (IEEE1547)int16s ×1000~0.16s0.16
0x030A7787781RWac_of_trip_level_1电网过频I段保护幅值(IEEE1547)int16Hz ×1000~4.5Hz0.5
0x030B7797791RWac_of_trip_time_1电网过频I段保护时间 (IEEE1547)int16s ×1000-300s2
0x030C7807801RWac_of_trip_level_2电网过频Ⅱ段保护幅值(IEEE1547)int16Hz ×1000~4.5Hz2
0x030D7817811RWac_of_trip_time_2电网过频Ⅱ段保护时间 (IEEE1547)int16s ×1000~10s0.16
0x030E7827821RWac_uf_trip_level_1电网欠频I段保护幅值(IEEE1547)int16Hz ×100-4.5~0Hz-1
0x030F7837831RWac_uf_trip_time_1电网欠频I段保护时间 (IEEE1547)int16s ×1000-300s2
0x03107847841RWac_uf_trip_level_2电网欠频Ⅱ段保护幅值(IEEE1547)int16Hz ×100-4.5~0Hz-2
0x03117857851RWac_uf_trip_time_2电网欠频Ⅱ段保护时间 (IEEE1547)int16s ×1000~10s0.16
0x03127867861RWreconnect_time电网恢复延时(IEEE1547)int16s ×135~300s50default value
0x03167907901RWAnti-islanding function孤岛检测enum16 Island detection 0: disabled
1: enabled
0 Anti-islanding is a CPUC RULE 21/HECO RULE14H/IEEE1547-requested function to make sure the inverter disconnect from the grid in case of blackout.
This is to prevent the formation of an unintended island. The inverter design shall comply with the requirements of IEEE Std 1547 and UL 1741 standards (or latest versions) and be certified to have anti-islanding protection such that the synchronous inverter will automatically disconnect upon a utility system interruption
0x03177917911RWFVRT function频率/电压穿越功能使能enum16 0: disabled
1: enabled
0Frequency and Voltage Ride-Through: The ability to withstand voltage or frequency excursions outside defined limits without tripping or malfunctioning
0x03187927921RWReactive power control mode无功功率调整模式enum16 Reactive power regulation mode 0: Constant reactive power
1: Volt-VAr enabled
2: Constant PF
3: Watt-PF enabled (VDE)
0Grid-tied mode only, voltage and frequency setpoint the only setpoints
0x03197937931RWPower rising mode功率变化模式:0-阶跃, 1-斜率enum16 Power change mode 0: step
1: ramp(soft-start)
0to define how the power changes
0x031A7947941RWActive power control mode有功功率调节模式: 0-恒定有功功率,禁用1/2/3
1-电压自动调节,在电压正常范围内按0执行,电压超过一定范围自动按电压偏差量调节有功功率
2-频率自动调节(Freq/Volt)在频率正常范围内按0执行,频率超过一定范围自动按偏差量调节有功功率
3-电压频率自动调节(Volt/Watt & Freq/Watt) 电压频率均正常时执行0,异常时执行Freq/Watt 优先于Volt/Watt
enum16 Active power regulation mode 0: Constant Active power
1: Volt-Watt enabled
2: Freq-Watt enabled
3: Volt-Watt + Freq-Watt enabled
0Grid-tied mode only, Volt-Watt control & Freq/Watt control means active power will be regulated by grid voltage/frequency following a curve/ramp rate given by HECO or CPUC or other local utility authority codes
0x031B7957951RWGrid voltage asymmetric detection电网电压不平衡检测使能enum16 Power grid voltage imbalance detection enable 0: disabled
1: enabled
1Grid-tied mode only, voltage and frequency setpoint the only setpoints
0x031C7967961RWcontinuous overvoltage detection连续过压检测使能enum16 Continuous overvoltage detection enable 0: disabled
1: enabled
1Grid-tied mode only
0x031D7977971RWGrid-existence detection on power-up并网开机电网检测使能enum16 Grid-connected power grid detection enable 0: disabled
1: enabled
1Grid-tied mode only, detect whether the grid is on-service at powered-up.
0x031E7987981RWNeutral floating detection缺N检测使能enum16 缺N检测使能 0: disabled
1: enabled
1Grid-tied mode only
0x031F7997991RWOff-grid black-start mode离网黑启动方式enum16 离网黑启动方式 0: disabled
1: enabled
0if disabled, the inverter will start the AC voltage, then close the relay. In some off-grid cases, such as there are inductive loads or transformer, the inrush exciting current will trip the inverter. Enabling this register, the inverter will close the relay first try to limit the current and start the voltage slowly
0x03208008001RWGrid code selection并网标准选择enum16 Select region 0: HECO 14H /CPUC 21 (UL 1741SA)
1:VDE4105
2:AS4777
0Grid-tied mode only
0x03288088081RWFloat charge voltage浮充电压int16V锂电池二者要设为相同×10200.0~800.0V550Vwhen implementing Lithium-ion batteries, these two registers MUST be set to the same
0x03298098091RWTopping charge volage恒压充电压int16V ×10200.0~800.0V550V
0x032A8108101RWCurrent from topping charging to float charging恒压充转浮充电流int16A锂电池设为0×100.0~90.0A10Awhen implementing Lithium-ion batteries, this register MUST be set to 0
0x032B8118111RWMax charging current最大充电电流int16AMaximum charging current×100.0~90.0A90Alimit the max DC currents, keep default if you don't need to
0x032C8128121RWMax discharging current最小充电电流int16AMinimum charging current×100.0~90.0A90Alimit the min DC currents, keep default if you don't need to
0x032D8138131RWLower voltage limit of battery protection电池电压下限保护阈值int16VBattery voltage lower protection threshold×10200.0~800.0V200V
0x032E8148141RWUpper voltage limit of battery protection电池电压上限保护阈值int16V ×10200.0~800.0V600Vthis register can't be set lower than 0x0328 and 0x0329
0x033C8288281RWFVRT: Over/High voltage stage I ride through voltage ratio过(高)压穿越I段幅值(比率)int16%Vrated 1001.10~1.201.1ratio * rated voltage, follow the FVRT table given by HECO or CPUC or other local utility authority codes
0x033D8298291RWFVRT: Over/High voltage stage II ride through voltage ratio过(高)压穿越II段幅值(比率)int16%Vrated 1001.10~1.201.2ratio * rated voltage, follow the FVRT table given by HECO or CPUC or other local utility authority codes
0x033E8308301RWFVRT: Under/Low voltage stage I ride through voltage ratio欠(低)压穿越I段幅值(比率)int16%Vrated 1000.50~0.880.8ratio * rated voltage, follow the FVRT table given by HECO or CPUC or other local utility authority codes
0x033F8318311RWFVRT: Under/Low voltage stage II ride through voltage ratio欠(低)压穿越II段幅值(比率)int16%Vrated 1000.50~0.880.6ratio * rated voltage, follow the FVRT table given by HECO or CPUC or other local utility authority codes
0x03408328321RWFVRT: Under/Low voltage stage III ride through voltage ratio欠(低)压穿越III段幅值(比率)int16%Vrated 1000.40-0.500.5ratio * rated voltage, follow the FVRT table given by HECO or CPUC or other local utility authority codes
0x03418338331RWFVRT: Over frequency stage I ride through frequency过频穿越I段频率int16HzBias from rated frequency1001~6Hz3Hzfollow the FVRT table given by HECO or CPUC or other local utility authority codes
0x03428348341RWFVRT: Over frequency stage II ride through frequency过频穿越II段频率int16HzBias from rated frequency1002~6Hz5Hzfollow the FVRT table given by HECO or CPUC or other local utility authority codes
0x03438358351RWFVRT: Under frequency stage I ride through frequency欠频穿越I段频率int16HzBias from rated frequency100-10~-0.1Hz-3Hzfollow the FVRT table given by HECO or CPUC or other local utility authority codes
0x03448368361RWFVRT: Under frequency stage II ride through frequency欠频穿越II段频率int16HzBias from rated frequency100-10~-0.1Hz-10Hzfollow the FVRT table given by HECO or CPUC or other local utility authority codes
0x03458378371RWFVRT: Over/High voltage stage I ride through trip time过(高)压穿越I段时间int16s 1000.08-12.00s12sfollow the FVRT table given by HECO or CPUC or other local utility authority codes
0x03468388381RWFVRT: Over/High voltage stage II ride through trip time过(高)压穿越II段时间int16s 1000.08-0.16s follow the FVRT table given by HECO or CPUC or other local utility authority codes
0x03478398391RWFVRT: Under/Low voltage stage I ride through trip time欠(低)压穿越I段时间int16s 10020.00-50.00s20sfollow the FVRT table given by HECO or CPUC or other local utility authority codes
0x03488408401RWFVRT: Under/Low voltage stage II ride through trip time欠(低)压穿越II段时间int16s 10010.00-50.00s10sfollow the FVRT table given by HECO or CPUC or other local utility authority codes
0x03498418411RWFVRT: Under/Low voltage stage III ride through trip time欠(低)压穿越III段时间int16s 1000.08-21.00s0.5sfollow the FVRT table given by HECO or CPUC or other local utility authority codes
0x034A8428421RWFVRT: Over frequency stage I ride through trip time过频穿越I段穿越时间int16s 1020-1000.00s20.s
0x034B8438431RWFVRT: Over frequency stage II ride through trip time过频穿越II段穿越时间int16s 1000-1000.00s0.1s
0x034C8448441RWFVRT: Under frequency stage I ride through trip time欠频穿越I段穿越时间int16s 1020-1000.00s20.s
0x034D8458451RWFVRT: Under frequency stage II ride through trip time欠频穿越II段穿越时间int16s 100-1000.00s0.1s
0x03508488481RWVolt-VAr: reference voltage Vref电压调无功:调节参考电压Vref(HECO)int16%Vratedratio10000.950~1.0501refer to HECO RULE 14, keep default value if no aware of it
0x03518498491RWVolt-VAr: V1, Voltage setpoint @ Q1电压调无功: 调节点V1int16%Vratedratio10000.820~1.0300.92ratio * rated voltage, Available only when reactive power regulation mode is set to Volt/Var(53626).
0x03528508501RWVolt-VAr: V2, Voltage setpoint @ Q2电压调无功: 调节点V2int16%Vratedratio10000.900~1.0500.98ratio * rated voltage, Available only when reactive power regulation mode is set to Volt/Var(53626).
0x03538518511RWVolt-VAr: V3, Voltage setpoint @ Q3电压调无功: 调节点V3int16%Vratedratio10000.950~1.1501.02ratio * rated voltage, Available only when reactive power regulation mode is set to Volt/Var(53626).
0x03548528521RWVolt-VAr: V4, Voltage setpoint @ Q4电压调无功: 调节点V4int16%Vratedratio10000.970~1.1801.06ratio * rated voltage, Available only when reactive power regulation mode is set to Volt/Var(53626).
0x03558538531RWVolt-VAr: Q1, Max capacitive reactive regulation电压调无功:最大容性无功调节量Q1int16%Sratedratio1000~0.60.3ratio * rated power, Available only when reactive power regulation mode is set to Volt/Var(53626).
0x03568548541RWVolt-VAr: Q2, Initial capacitive reactive regulation电压调无功:初始容性无功调节量Q2int16%Sratedratio1000~0.60ratio * rated power, Available only when reactive power regulation mode is set to Volt/Var(53626).
0x03578558551RWVolt-VAr: Q3, Initial inductive reactive regulation电压调无功:初始感性无功调节量Q3int16%Sratedratio1000~0.60refer to HECO RULE 14, keep default value if no aware of it
0x03588568561RWVolt-VAr: Q4, Max inductive reactive regulation 电压调无功:最大感性无功调节量Q4int16%Sratedratio1000~0.60.3refer to HECO RULE 14, keep default value if no aware of it
0x03598578571RWVolt-VAr: response time电压调无功:调节反应时间int16s 1001~90s10srefer to HECO RULE 14, keep default value if no aware of it
0x035E8628621RWVolt-Watt: initial voltage Vstart过压降有功起始调节点Vstartint16%Vratedratio10001.010~1.2001.06ratio * rated voltage, Available only when active power regulation mode(53636) is set to Volt/Watt and operating in discharge mode. Follow the FVRT table given by HECO or CPUC or other local utility authority codes.
0x035F8638631RWVolt-Watt: end voltage Vstop过压降有功终止调节点Vstopint16%Vratedratio10001.020~1.2001.1refer to HECO RULE 14, keep default value if no aware of it
0x03608648641RWVolt-Watt: initial power Pstart过压降有功起始功率Pstartint16%Ppresentratio1000.00~1.001refer to HECO RULE 14, keep default value if no aware of it
0x03618658651RWVolt-Watt: end power Pstop过压降有功终止功率Pstopint16%Ppresentratio1000.00~1.000refer to HECO RULE 14, keep default value if no aware of it
0x03628668661RWVolt-Watt: return to service delay过压降有功恢复延时int16s 1003~90s60sTo set the output power recovery time delay after the utility voltage returns to normal
0x03638678671RWVolt-Watt: response time过压降有功反应时间int16sCPUC rule 21 only1000.5-60s10srefer to HECO RULE 14, keep default value if no aware of it
0x03648688681RWFreq-Watt(Discharge): start of frequency drop 放电过频降有功起始点int16HzBias from rated frequency1000.1-1Hz0.1Available only when active power regulation mode(53636) is set to Freq/Watt and operating in discharge mode. When the actual frequency is above the point, the active power will be regulated(lowered) with the ramp rate
In Australia, this register shall be fixed to 0.25Hz
0x03658698691RWFreq-Watt (Discharge): slope of frequency drop放电过频降有功调节斜率int16%Ppresent/Hzratio1000.02~0.070.05The ramp rate is defined as multiple of set active power per hertz that above the above the Freq/Watt regulation point.Available only when active power regulation mode(53636) is set to Freq/Watt and operating in discharge mode. Example: Rated frequency is 60Hz, the target active power is set to 10kW, Freq/Watt regulation point is set to 2Hz, ramp rate is set as 0.5. If the actual frequency reaches 63Hz, the output active power will be 10kW-(63Hz-62Hz)×0.5*(10kW/Hz) = 5kW
0x03668708701RWFreq-Watt (Discharge) (Australia only): Fstop-DISCH放电过频降有功终点(用于澳洲认证)int16HzAS4777 only, bias from rated frequency1000.26~3Hz2
0x03678718711RWFreq-Watt(Charge)(Australia only): Fstop-CH充电欠频降有功终点(用于澳洲认证)int16HzAS4777 only, bias from rated frequency100-0.26~-4Hz-1
0x03688728721RWVolt-Watt (Charge)(Australia only) : Vstart-CH充电欠压降有功起始点(用于澳洲认证)int16%VratedAS4777 only, ratio10000.900~1.0000.957
0x036C8768761RWSoft-start Ramp Rate(SS)软启功率变化速率int16%Prated/sratio100000.001~3 3SS takes effect when the inverter starts or when the inverter is on grid reconnection after the trip caused by FVRT timeout
0x036D8778771RWPower Ramp Rate(RR)功率变化速率int16%Prated/sEnable first100000.001~33RR takes effect in Volt-Watt or Freq-Watt mode when the grid is back to normal state and the inverter tring to go back to normal output. In other words, as long as the inverter doesn’t trip, and the inverter had derated the output power. RR takes effect when the inverter tries to go back to normal output.
Available only when Power rising mode is set to ramp mode(53626).
If the value is 2.000, it means within 0.5 seconds the system can runs to full power output.
0x036E8788781RWTarget PF 目标功率因数int16 100-1~+1
-: inductive +: capacitve
1Available only when Constant PF is enabled
0x036F8798791RWWatt-PF: P1有功调节功率因数: 有功调节点P1int16%Pratedratio1000.20~1.000.02Available only when active power regulation mode(53636) is set to Freq/Watt and operating in discharge mode. When the actual frequency is above the point, the active power will be regulated(lowered) with the ramp rate
0x03708808801RWWatt-PF: P2有功调节功率因数: 有功调节点P2int16%Pratedratio1000.20~1.000.5
0x03718818811RWWatt-PF: P3有功调节功率因数: 有功调节点P3int16%Pratedratio1000.20~1.000.7
0x03728828821RWWatt-PF: P4有功调节功率因数: 有功调节点P4int16%Pratedratio1000.20~1.001
0x03738838831RWWatt-PF: PF1有功调节功率因数: 功率因数调节点PF1int16 100-0.90~0.901
0x03748848841RWWatt-PF: PF2有功调节功率因数: 功率因数调节点PF2int16 100-0.90~0.901
0x03758858851RWWatt-PF: PF3有功调节功率因数: 功率因数调节点PF3int16 100-0.90~0.90-0.96
0x03768868861RWWatt-PF: PF4有功调节功率因数: 功率因数调节点PF4int16 100-0.90~0.90-0.9
0x03778878871RWcontinous over voltage trip threshold in 10 minutes10分钟连续过压保护幅值int16%Vratedratio1001.06~1.121.1
0x03788888881RWfrequency variation rate trip threshold电网频率变化率超额保护阈值int16 0: disabled
1: rate limit 0.125Hz/s
2: rate limit 0.2Hz/s
0
0x03798898891RWPhase angle abrupt trip threshold电网相角突变保护阈值int16 0: disabled,\\1: angle abrupt limit 12°
2: angle abrupt limit 6°
0
0x037A8908901RWGrid Reconnection: voltage upper limit电网重连上限电压(VDE)int16%Vratedratio10001.00~1.151.1Available only when Power rising mode is set to ramp mode.
once tripped after FVRT timeout, the inverter can reconnect to the grid when frequency or voltage is back to the thresholds defined as grid is back to service. In HECO14 /CPUC 21, this register is unnecessary to
0x037B8918911RWGrid Reconnection: voltage lower limit电网重连下限电压(VDE)int16%Vratedratio10000.80~1.000.85
0x037C8928921RWGrid Reconnection: frequency upper limit电网重连上限频率int16HzBias from rated frequency1000~0.15Hz0.05HzAvailable only when Power rising mode is set to ramp mode once tripped after FVRT timeout, the inverter can reconnect to the grid when frequency or voltage is back to the thresholds defined as grid is back to service
0x037D8938931RWGrid Reconnection: frequency lower limit电网重连下限频率int16HzBias from rated frequency100-3~0Hz-2.5Hz
0x0FA1400140066WTime setting - Year\Month\Day\Hour\Minute\Second uint16 YYYYMMDDHHmmss
OPTIONAL BMS FORWARDING SECTION- START
0xF00161441614421RBattery total voltage电池总电压uint16V BMS protocol for Vendor A
0xF00261442614431RBattery total current电池总电流int16A BMS protocol for Vendor A
0xF00361443614441RBattery SOC uint16 BMS protocol for Vendor A
0xF00461444614451RBattery SOH uint16 BMS protocol for Vendor A
0xF00561445614461RBattery status bits uint16 BMS protocol for Vendor A
0xF00661446614471RBattery error bits uint16 BMS protocol for Vendor A
0xF00761447614481RBattery error bits uint16 BMS protocol for Vendor A
0xF00861448614491RBattery error bits uint16 BMS protocol for Vendor A
0xF00961449614501RMin temperature最低温度int16C BMS protocol for Vendor A
0xF00A61450614511RMin temperature index最低温度指数uint16 BMS protocol for Vendor A
0xF00B61451614521RMax temperature最高温度int16C BMS protocol for Vendor A
0xF00C61452614531RMax temperature index最高温度指数uint16 BMS protocol for Vendor A
0xF00D61453614541RAverage temperature平均温度int16C BMS protocol for Vendor A
0xF00E61454614551RAverage voltage平均电压uint16V BMS protocol for Vendor A
0xF00F61455614561RMin voltage最小电压uint16V BMS protocol for Vendor A
0xF01061456614571RMin voltage index最小电压指数uint16 BMS protocol for Vendor A
0xF01161457614581RMax voltage最大电压uint16V BMS protocol for Vendor A
0xF01261458614591RMax voltage index最大电压指数uint16 BMS protocol for Vendor A
0xF01361459614601RMax Allow charge current最大允许充电电流uint16A BMS protocol for Vendor A
0xF01461460614611RMax Allow discharge current最大允许放电电流uint16A BMS protocol for Vendor A
0xF01561461614621RBMS firmware version_LMU uint16 BMS protocol for Vendor A
0xF01661462614631RBMS firmware version_BMU uint16 BMS protocol for Vendor A
0xF01761463614641RBMS firmware version_Top BMU uint16 BMS protocol for Vendor A
0xF01861464614651RBMS hardware version_LMU uint16 BMS protocol for Vendor A
0xF01961465614661RBMS hardware version_BMU uint16 BMS protocol for Vendor A
0xF01A61466614671RBMS hardware version_Top BMU uint16 BMS protocol for Vendor A
0xF01B61467614681R1~16 Cluster status uint16 BMS protocol for Vendor A
0xF01C61468614691R17~20 Cluster status uint16 BMS protocol for Vendor A
OPTIONAL BMS FORWARDING SECTION- END
0x0260 Operation enum16 list
enum16St OFF关机1
enum16St SLEEPING (NOT implemented yet)睡眠(未启用)2
enum16St STARTING (NOT implemented yet)开机中3
enum16St MPPT (NOT implemented yet)MPPT(未启用)4
enum16St THROTTLED限流5
enum16St SHUTTING_DOWN (NOT implemented yet)关机中6
enum16St FAULT故障7
enum16St STANDBY待机8
enum16St STARTED已启动9
0x0262 Event bitfield32 list
bitfield32Evt1 GROUND_FAULT接地故障0
bitfield32Evt1 DC_OVER_VOLT直流侧过压1
bitfield32Evt1 AC_DISCONNECTAC继电器断开2
bitfield32Evt1 DC_DISCONNECTDC继电器断开3
bitfield32Evt1 GRID_DISCONNECT电网断开4
bitfield32Evt1 CABINET_OPEN (NOT implemented yet)机柜打开(未启用)5
bitfield32Evt1 MANUAL_SHUTDOWN手动关机6
bitfield32Evt1 OVER_TEMP过温7
bitfield32Evt1 OVER_FREQUENCY过频8
bitfield32Evt1 UNDER_FREQUENCY欠频9
bitfield32Evt1 AC_OVER_VOLTAC过压10
bitfield32Evt1 AC_UNDER_VOLTAC欠压11
bitfield32Evt1 BLOWN_STRING_FUSE (NOT implemented yet)保险已烧(未启用)12
bitfield32Evt1 UNDER_TEMP (NOT implemented yet)温度过低(未启用)13
bitfield32Evt1 MEMORY_LOSS内存错误14
bitfield32Evt1 HW_TEST_FAILURE (NOT implemented yet)硬件检测失败(未启用)15