Communication connection
Bottom view
No. | Description |
---|---|
1 | DC waterproof tube + |
2 | DC waterproof tube - |
3 | Ethernet waterproof terminal |
4 | RS-485 waterproof terminal |
5 | R-EPO waterproof terminal |
6 | AC waterproof tube |
7 | AC disconnect |
8 | Fan box |
PWS2-30K-NA has two different communication interfaces: Ethernet and RS-485, meanwhile, there is a remote emergency power off terminal.
At a same time, the PWS2-30K-NA can only be configured to communicate with the EMS via Ethernet, or RS-485, refer to HMI operation for more information
Ethernet cable connection
PWS2-30K-NA can be directly controlled through Ethernet for remote control. Through networking, users can remote dispatch energy, monitor operation status, and set parameters with MODBUS TCP/IP protocol.
The pinout of a standard T-568B straight-through ethernet cable:
Pin | Color |
---|---|
1 | white/orange |
2 | Orange |
3 | white/green |
4 | blue |
5 | white/blue |
6 | green |
7 | white/brown |
8 | brown |
- Penetrate network cable whose insulating layer is stripped into the waterproof cap and insert it into RJ45 connector after being arranged in order;
- Use wire crimpers to compress the connector;
- Screw out the cap on the waterproof Ethernet terminal at the bottom of the inverter;
- Insert the ready-made cable into Ethernet terminal.
RS-485 cable connection
PWS2-30K-NA can be connected to EMS through RS-485 to obtain battery information and energy dispatching command and complete automatic charging and discharging control and protection of energy storage system. RS-485 is connected through RJ45 connector. The definition of the pin of RJ45 connector is shown in the following image. The connection steps are the same as Ethernet cable.