Recommended grid-support settings

Page Parameter on HMI Meaning How to set
Setting → AC → Page 2 Anti-islanding to dis-/enable Anti-islanding Set to Enabled
Page Parameter on HMI Meaning How to set
Setting → AC → Page 2 FVRT enable to dis-/enable frequency and voltage ride-through Set to Enabled
Setting → AC → Page 2 FVRT current limit to dis-/enable current limiting in ride-through California: Enabled
Other regions: Disabled
Page Parameter on HMI Meaning How to set
Setting → AC → Page 6 OFR# voltage Over-frequency region # boundary , bias of nominal frequency OFR1 frequency: 3 (+60Hz)
OFR2 frequency:
  • 5 (+60Hz) for Molokai, Lanai
  • 4 (+60Hz) for Oahu, Maui, Hawaii
Setting → AC → Page 6 OFR# time Over-frequency region # trip time, -0.5~-1s later than ride-through until OFR1 time: 20 s, making ride-through 19.98 s
OFR2 time: 0.1s, no ride through
Setting → AC → Page 6 UFR# voltage Under-frequency region # boundary, bias of nominal frequency OFR1 frequency: -3 (+60Hz)
OFR2 frequency:
  • -10 (+60Hz) for Molokai, Lanai
  • -4 (+60Hz) for Oahu, Maui, Hawaii
Setting → AC → Page 6 UFR# time Under-frequency region # trip time, -0.5~-1s later than ride-through until UFR1 time: 20 s, making ride-through 19.98 s
UFR2 time: 0.1s, no ride through
Setting → AC → Page 6 Restore upper limit freq Grid reconnect threshold frequency-upper limit, bias of nominal frequency 0.1 (+60Hz)
Setting → AC → Page 6 Restore lower limit freq Grid reconnect threshold frequency-lower limit, bias of nominal frequency -0.1 (+60Hz)
Page Parameter on HMI Meaning How to set
Setting → AC → Page 5OVR# voltage Over-voltage region # boundary, ratio of nominal voltage OVR1 voltage: 1.1 (*480V)
OVR2 voltage: 1.2 (*480V)
Setting → AC → Page 5OVR# time Over-voltage region # trip time, 0.02s later than ride-through until OVR1 time: 0.94 s, making ride-through until 0.92s
OVR2 time: 0.1 s, no ride-through
Setting → AC → Page 5UVR# voltage Under-voltage region # boundary, ratio of nominal voltage UVR1 voltage: 0.88 (*480V)
UVR2 voltage: 0.7 (*480V)
UVR3 voltage: 0.5 (*480V)
Setting → AC → Page 5UVR# time Under-voltage region # trip time, 0.02s later than ride-through until UVR1 time: 20 s, making ride-through until 19.98s
UVR2 time: 11 s, making ride-through until 10.98s
UVR3 time: 0.1 s, no ride-through
Page Parameter on HMI Meaning How to set
Setting → AC → Page 2 P change mode How the power changes when instructed, step or with ramp Set to “Ramp rate” to enable SS and RR
Setting → AC → Page 1 Soft-Start reconnection ramp rate SS <0.0032 (*Pnom/s)
Setting → AC → Page 1 Grid reconnection delay Grid reconnection delay 300 s
Setting → AC → Page 1 Normal Ramp Rate RR 1 (*Pnom/s)
Page Parameter on HMI Meaning How to set
Setting → AC → Page 1 AC operation mode to enable Votl-VAr control Set to V/VAr control to apply Votl-VAr control
Setting → AC → Page 7 Volt/var point 1 V1 at Q1, ratio of nominal voltage 0.92 (*480V)
Setting → AC → Page 7 Volt/var point 2 V2 at Q2, ratio of nominal voltage 0.97 (*480V)
Setting → AC → Page 7 Volt/var point 3 V3 at Q3, ratio of nominal voltage 1.03 (*480V)
Setting → AC → Page 7 Volt/var point 4 V4 at Q4, ratio of nominal voltage 1.07 (*480V)
Setting → AC → Page 7 Max. inductive reactive regulation Q4, ratio of nominal capacity 0.3 (*Pnom)
Setting → AC → Page 7 Max. capacitive reactive regulation Q1, ratio of nominal capacity 0.3 (*Pnom)
Setting → AC → Page 7 Initial. inductive reactive regulation 3 Q3, ratio of nominal capacity 0 (*Pnom)
Setting → AC → Page 7 Initial. capacitive reactive regulation 2 Q2, ratio of nominal capacity 0 (*Pnom)
Setting → AC → Page 7 Volt/var reaction time Volt-VAr response time 1 s
Setting → AC → Page 7 Volt/var Vref Vref, ratio of nominal voltage 1 (*480V)
Page Parameter on HMI Meaning How to set
Setting → AC → Page 2 Active power regulation Set to Volt control to apply Volt-Watt Unaware of present CPUC/HECO politics
Setting → AC → Page 2 Active power regulation Set to Freq control to apply Freq-Watt Unaware of present CPUC/HECO politics
Setting → AC → Page 2 Active power regulation Set to V/F control to apply Volt-Watt and Freq-Watt at the same time. Yet Freq-Watt prior to Volt-Watt Unaware of present CPUC/HECO politics
Page Parameter on HMI Meaning How to set
Setting → AC → Page 8 Volt/Watt V1 Volt-Watt V1 1.06 (*480V)
Setting → AC → Page 8 Volt/Watt ramp rate useless, cancelled in V1440 0
Setting → AC → Page 8 Volt/Watt delay Volt/Watt return delay 60 s
Setting → AC → Page 8 Volt/Watt V2 Volt-Watt V2 1.1 (*480V)
Setting → AC → Page 8 Volt/Watt P1 Volt-Watt P1 1 (*power setpoint)
Setting → AC → Page 8 Volt/Watt P2 Volt-Watt P2 0 (*power setpoint)
Setting → AC → Page 8 Volt/Watt response time Volt-Watt response time10 s
Page Parameter on HMI Meaning How to set
Setting → AC → Page 8 Freq/Watt point Fstart, the frequency Freq-Watt supposed to start 0.25 (+60Hz)
Setting → AC → Page 8 Freq/Watt ramp rate Freq-Watt slope 0.05 (*power setpoint/Hz)
Setting → AC → Page 8 Freq-Watt response time Freq-Watt response time 0.50 s