Fault name | Triggering criterion | System phenomenon | Screening method |
---|---|---|---|
AC overvoltage | Ac side line voltage > 1.2* rated voltage for 160ms or AC side line voltage > 1.15* rated voltage for 2s or When the model is equipped with a transformer the AC side phase voltage > 1.2* rated voltage for 160ms or When the model is equipped with a transformer the AC side line voltage > 1.15* rated voltage for 2s | Warning ‘AC1-10 AC overvoltage' the AC module is turned off and the history Warning record is automatically entered after the fault disappears. | 1. Check system Settings –U2 board – yes/no should be set to ‘yes'; 2. check the output voltage system settings whether it matches the actual transformer; 3. Measure whether the AC line voltage and AC phase voltage are overvoltage |
AC undervoltage | AC side line voltage < 0.45 * rated voltage for 160ms or AC side line voltage < 0.6* rated voltage for 1s or AC side line voltage < 0.8* rated voltage for 2s or When the model is equipped with a transformer, the AC side line voltage < 0.45* rated voltage for 160ms or When the model is equipped with a transformer, the AC side line voltage < 0.6* rated voltage for 1s or When the model is equipped with a transformer, the AC side line voltage < 0.8* rated voltage for 2s“ | Warning ‘AC1-10 AC undervoltage', the AC module is turned off, and the history Warning record is automatically entered after the fault disappears. | 1. Check system Settings –U2 board – yes/no, should be set to ‘yes'; 2. Check the output voltage system settings, whether it matches the actual transformer; 3. Measure whether the AC line voltage and AC phase voltage are overvoltage; 4. Both steps 1 and 2 are normal.Check whether the AC voltage of the main wiring diagram interface is normal. If there is no voltage, the sampling line may be connected incorrectly. |
AC overfrequency | AC side frequency > 52Hz for 160ms or AC side frequency > 51.5Hz for 2s | Warning ‘AC1-10 AC overfrequency', the AC module is turned off, and the history Warning record is automatically entered after the fault disappears. | 1. Check system Settings –U2 board – yes/no, should be set to ‘yes'; 2. Check the monitoring page - whether the AC frequency is normal |
AC underfrequency | Ac side frequency < 47Hz for 160ms or AC side frequency > 49Hz for 2s | Warning‘AC1-10 AC underfrequency', the AC module is turned off, and the history Warning record is automatically entered after the fault disappears. | 1. Check system Settings –U2 board – yes/no, should be set to ‘yes'; 2. Check the monitoring page - whether the AC frequency is normal |
Grid connectivity switching errors | In off-grid mode, the grid has electricity for 1s. | Warning ‘AC1-10 AC grid connectivity switching errors', the AC module is turned off, and the history Warning record is automatically entered after the fault disappears. | With the STS models 1. System setting – system parameters – type of inverter shall be set as' micro grid STS inverter '; 2. System information – module status –STS and U2 should be online, and the communication line from STS module to U2 board should be connected correctly; Without STS models When the monitoring is set to off-grid, the AC switch should be disconnected |
AC antitone | The AC frequency is between [-45hz, -65hz] for 1s. | Warning ‘AC1-10 AC antitone', the AC module is turned off, and the history Warning record is automatically entered after the fault disappears. | Check whether the phase sequence of the AC incoming line is reversed |
Module current asymmetric | Grid three-phase current Max - min >25% rated current The maximum three-phase cu”“Grid three-phase current maximum - minimum > 25% rated current AND Grid three-phase current maximum > 10% rated current for 30s”“rrent of the grid is >10% of the rated current for 30s | Warning ‘AC1-10 module current asymmetric', the AC module is turned off, triggering AC fault record and the history Warning record is automatically entered after the fault disappears.” | Check whether phase is missing from AC incoming line to transformer and whether phase is missing from AC side of transformer to AC module |
DC input overvoltage | Single-stage model: Bus voltage > (topping charge voltage +8V) for 2s or Bus voltage > (topping charge voltage +28V) for 200ms or Bus voltage > 930V for 8ms or Bus voltage > 935V for 1ms or Positive bus voltage > 480V for 1ms or Negative bus voltage > 480V for 1ms Two-stage model: Off-grid mode, bus voltage > 880V for 2s or Bus voltage > 900V for 200ms or Bus voltage > 930V for 8ms Grid-tied mode, bus voltage > 920V for 2s or Bus voltage > 940V for 200ms or Bus voltage > 930V for 8ms or Bus voltage > 935V for 1ms or Positive bus voltage > 480V for 1ms or Negative bus voltage > 480V for 1ms“ | Warning ‘AC1-10 DC input overvoltage', the AC module is turned off, triggering AC fault record, and the history Warning record is automatically entered after the fault disappears. | 1. The topping charge voltage should be greater than the actual input DC voltage; 2. Check whether the fault is caused by DC source problems |
Emergency stop | The emergency stop input dry contact is detected as low level for 20ms | Warning‘AC10-11 emergency stop', the AC module is turned off, the AC fault record is triggered, and transmitted to the U2 board. After the fault is recovered, it can be manually cleared. After the fault disappears, the historical Warning record is automatically entered. | 1, EPO is pressed; 2. The EPO terminal is wired incorrectly |
Low DC voltage | AC soft start mode, the fault is not detected before the AC is turned on; Two-stage model, DC soft start mode, this fault is not detected before the DC is turned on; (Single-stage DC source mode judgement voltage is: float charge voltage and uncontrollable rectifier voltage + 30V maximum value) (Single-stage battery mode judgment voltage is: EOD voltage and uncontrollable rectifier voltage + 30V maximum value) (Two-stage optical storage integrated judgment voltage is: topping charge voltage, uncontrollable rectifier voltage + 10V maximum value) (The two-stage photovoltaic bus judgement the voltage is: MPPT voltage, uncontrollable rectifier voltage + 10V maximum value) Bus voltage < Judgment voltage - 50V for 4s OR Bus voltage < Judgment voltage - 90V for 400ms OR Bus voltage < Judgment voltage - 250V for 40ms OR Bus voltage < Judgment voltage - 350V for 8ms | Warning‘AC1-10 low DC voltage', the AC module is turned off, triggering AC fault record , and the history Warning record is automatically entered after the fault disappears. Note: The Warning is triggered 10 times from scratch, or the Warning is continued within 1 hour. The Warning will be locked for 24 hours, the DC switch will trip, and the AC fault record will be triggered. If the voltage is restored after 24 hours of automatic power-on, the Warning will be cleared automatically. | Single-stage model, please check if the EOD voltage is set too high (EOD voltage should be <battery voltage); Two-stage model, please check if the topping charge voltage is set too low (the topping charge voltage should be > battery voltage); If the above steps are correct and the DC switch is tripped, the Warning has been triggered multiple times and locked. Please check the battery discharge condition and power on again for confirmation |
Bus overvoltage | Positive bus voltage > 470V for 8ms OR Negative bus voltage >470V for 8ms | Warning‘AC1-10 bus overvoltage', the AC module is turned off, triggering AC fault record , and the history Warning record is automatically entered after the fault disappears | 1. Check if the positive and negative bus calibration is corrected; 2. Check whether there is any problem with the N-row connection method for multi-branch models; 3. No transformer may also cause the fault; |
Radiator overtemperature | Module temperature > 105°C for 10s OR Module temperature > 110°C for 500ms OR Power port temperature > 99°C for 500ms | Warning‘AC1-10 Radiator overtemperature', the AC module is turned off, triggering AC fault record , and the history Warning record is automatically entered after the fault disappears. Note: Module temperature >110 °C and power port temperature >99 °C will cause DC switch trip. | 1. Check whether the module fan is faulty;\\2. Check whether the cooling hole of the module is blocked |
Fan fault | Fan fault input dry contact is low level, lasting for 1s | Warning‘AC1-10 fan fault', the AC module is turned off, triggering AC fault record , can be manually cleared, and the history Warning record is automatically entered after the fault disappears.Note: Module temperature >110 °C and power port temperature >99 °C will cause DC switch trip | Replace the module |
Dc relay open circuit | After the DC main relay is closed, the detection starts. The voltage difference between the two ends of the relay (bus voltage - positive bus - negative bus) > 20V, lasting for 200ms | Warning‘AC1-10 DC relay open circuit', triggering AC fault record , can be manually cleared, and the history Warning record is automatically entered after the fault disappears. | Replace the module |
Calibration parameters abnormal | There are analog quantities that are not calibrated | Warning‘AC1-10 calibration parameter abnormal'. After the fault disappears, it will be automatically entered into the historical Warning record, which will not affect the starting up, and can be cleared by re-energizing after calibration | Eliminate after calibrating analog quantity |
Output overload | Maximum value of three-phase AC active and apparent power > 1.1 * rated voltage for 160ms OR Maximum value of three-phase AC current > 1.1 * rated voltage for 160ms OR DC current > 110A for 160ms | Warning‘AC1-10 output overload', the Warning will not be turned off | AC overloaded under the off-grid;\\DC overload or DC output short circuit in Dc source mode;IGBT short circuit |
Fuse fault | Fuse fault input dry contact is low level for 1s | Warning‘AC1-10 fuse fault', the AC module is turned off, triggering AC fault record , can be manually cleared, and the history Warning record is automatically entered after the fault disappears | Replace the fuse |
Monitoring setting fault | After the module is powered on, the parameters of the monitoring batch are not received for 100s | Warning‘AC1-10 monitoring setting fault', the AC module is turned off, and the history Warning record is automatically entered after the fault disappears | 1. The module dialing code cannot exceed the number of modules; 2. The number of AC parallel units monitored and set is incorrect (should be greater than or equal to the number of AC modules); 3. Record the U2 board and monitor version number |
DC soft start fault | AC soft start During the startup process (DC soft start relay is closed), the voltage difference across the relay (bus voltage - positive bus - negative bus ) > 45V for 60s; DC soft start During the startup process (DC soft start relay is closed), the voltage difference across the relay (bus voltage - positive bus - negative bus) > 30V for 90s OR During the startup process (DC main relay is closed), the voltage difference across the relay (bus voltage - positive bus - negative bus ) > 20V for 120s | Warning‘AC1-10 DC soft start fault”, the AC module is turned off, triggering the AC fault record, which can be manually cleared. After the fault disappears, it will automatically enter the historical Warning record and automatically clear the Warning within 24 hours | DC soft start relay is open circuit damaged Dc main relay is open circuit damaged; Dc soft start resistor is damaged; IGBT open circuit or auxiliary power supply problems |
CAN A communication fault | CanA bus does not receive monitoring communication data for 50s | Warning‘AC1-10 CanA communication fault', the AC module is turned off, and the history Warning record is automatically entered after the fault disappears. | Check whether the module communication line is firmly connected and whether the CanA jumper cap is correct |
U2 communication exception 2 | CanB bus does not receive U2 board communication data for 100ms;\\ | Warning‘AC1-10 U2 communication exception 2', the history Warning record is automatically entered after the fault disappears | Check whether the module communication line is firmly connected and whether the CanB jumper cap is correct |
AC soft start fault | AC soft start During the startup process (AC soft start relay is closed), the internal bus voltage < (two-phase uncontrolled rectification voltage +5V) for 120s OR During the startup process (AC main relay is closed), internal bus voltage < (three-phase uncontrolled rectification voltage + 30V) for 90s; DC soft start During the startup process (the DC main relay is closed), the phase lock is not completed within 10s of the grid-tied mode (the voltage across the AC relay is inconsistent), and the inverter voltage is abnormal within 10s of the off-grid mode (the amplitude is less than 10% of the rated value or Phase and phase-locked loop are more than 10°) | Warning‘AC1-10 AC soft start fault', the AC module is turned off, triggering AC fault record , can be manually cleared, and the history Warning record is automatically entered after the fault disappears. | Check if the soft start mode is set incorrectly; Check if the AC soft start resistor is damaged. Check if the AC soft start relay and AC main relay are damaged |
Output overload timeout | One or more of the inverter current/inverter power/DC current overload timeout criterion and the short circuit criterion are triggered. Inverter current overload timeout criterion: Module inverter current three-phase maximum > 1.5 * rated current for 120ms OR Module inverter current three-phase maximum > 1.3 * rated current for 200ms OR Module inverter current three-phase average > 1.25 * rated current for 200ms OR Module inverter current three-phase maximum > 1.2 * rated current for 1min OR Module inverter current three-phase maximum > 1.1 * rated current for 10min Inverter power overload timeout criterion: Module inverter power three-phase maximum > 1.5 * rated power rated for 120ms OR Module inverter current three-phase maximum > 1.3 * rated current for 200ms OR Module inverter current three-phase average > 1.25 * rated currentfor 200ms OR Module inverter current three-phase maximum > 1.2 * rated current for 1min OR Module inverter current three-phase average > 1.15 * rated current for 1min OR Module inverter current three-phase maximum > 1.15 * rated current for 5min OR Module inverter current three-phase maximum > 1.1 * rated current for 10min DC current overload timeout criterion DC current > 135A for 500ms OR DC Current > 125A for 90s OR DC Current > 115A for 945s dc current>125A lasting 90s OR dc current > 115A, lasting 945s | Warning‘AC1-10 output overload timeout', the AC module is turned off, the AC fault record is triggered, and the history Warning record is automatically entered after the fault disappears. Note: the Warning will be triggered 3 times from scratch. The Warning will be locked for 1 hour, and will be cleared if there is no fault after 1 hour | Check whether the power line is short-circuited; Check whether there is a calibration problem; If running in off-grid mode, check whether the AC load is too large; If running in grid-tied mode, check whether the AC is out of phase or short circuit |
Output voltage abnormal | Off-grid boot operation, \\{Inverter Voltage - Output Voltage } > 60V for 400ms (Inverter Voltage - Output Voltage) > 120V for 80ms | Warning “ac1-10 output voltage abnormal”, the AC module is turned off, triggering AC fault record, can be manually cleared, and the history Warning record is automatically entered after the fault disappears | |
Synchronous signal fault 1 | The descending edge cannot be detected by the power frequency bus, lasting for 100ms | Warning‘AC1-10 synchronous signal fault 1', the AC module is turned off, and the history Warning record is automatically entered after the fault disappears | Check whether the module communication terminal is firmly connected, and then power on to check again; replace the module |
DSP version fault | After power on, the bootloader version does not pass the matching test | Warning‘AC1-10 DSP version fault', the AC module is turned off, and the history Warning record is automatically entered after the fault disappears | Re-upgrade the U1 board program with the emulator |
Sampling zero anomaly | U1 board without tooling correction | Warning‘AC1-10 sampling zero anomaly', the history Warning record is automatically entered after the fault disappears | Replace the U1 board |
U2 communication exception 1 | AC module CanA mailbox 3 did not receive U2 board communication data for 60s | Warning‘AC1-10 U2 communication exception 1', the history Warning record is automatically entered after the fault disappears | Check the monitoring page to see if the U2 board is online. If the U2 board is not online, check whether the matching resistor and jumper cap are correct; If the U2 board is online, check whether the software version number of the U2 board and the software version number of the U1 board are correct.\\Replace the U2 board |
15V power fault | Auxiliary power fault input dry contact is abnormal, and it will be reported for 2s | Warning‘AC1-10 15V power fault', the AC module is turned off, the AC fault record is triggered, and the history Warning record is automatically entered after the fault disappears | Check if the auxiliary power supply voltage is normal, or replace the auxiliary power supply board |
Grid voltage asymmetric | Off-grid mode does not judge the fault; Grid-tied mode AC line voltage three-phase maximum > 17% of rated voltage && AC voltage asymmetric > 4% for 10s | Warning‘AC1-10 grid voltage asymmetric', the AC module is turned off, the AC fault record is triggered, and the history Warning record is automatically entered after the fault disappears. Note: The asymmetric criterion is triggered 3 times, the Warning is locked, and it is cleared after 1h without fault | Measuring whether the voltage of the three-phase grid is normal; Check if the AC power line is out of phase |
Module heavy number fault | There are two or more AC modules with the same dialing code | Warning‘AC1-10 module repeat fault', the AC module is turned off, and the history Warning record is automatically entered after the fault disappears. Note: the fault is handled as the deleted module | Check if the dial code is correct |
485 communication fault | The AC module did not receive the monitoring data request for 120s | Warning‘AC1-10 485 communication fault', the AC module is turned off, and the history Warning record is automatically entered after the fault disappears | Check if the AC module communication terminal and monitoring communication terminal wiring are loose |
CanB communication fault | The communication data was not received between the AC modules for 10ms | Warning‘AC1-10 CanB communication fault', the AC module is turned off, and the history Warning record is automatically entered after the fault disappears | Check whether the AC module communication terminal and X2 board terminal wiring are loose. Check if the matching resistor and jumper cap are correct |
CPLD version fault | The CPLD version compatibility judgment does not pass, lasting 100ms | Warning‘AC1-10 CPLD version fault', the AC module is turned off, and the history Warning record is automatically entered after the fault disappears. | Re-program DSP and CPLD with emulator |
Hardware version fault | After power-on, it is detected that the two internal dialing codes of the module are set to 10 for 100ms | Warning‘AC1-10 hardware version fault', the AC module is turned off, and the history Warning record is automatically entered after the fault disappears | The two internal dialing codes of the module are set to 01 |
Dc relay short circuit | Just judge when both the DC main relay and the soft start relay are disconnected: External bus voltage > (three-phase uncontrolled rectification voltage - 50V) && External bus voltage - Internal bus voltage < 20V for 90s | Warning‘AC1-10 dc relay short circuit', the AC module is turned off, triggering AC fault record , can be manually cleared, and the history Warning record is automatically entered after the fault disappears | Check whether the AC module dc voltage and positive and negative bus voltage calibration is correct Replace the AC module |
Bus undervoltage | (Positive bus voltage < 200V OR Negative bus voltage < 200V) && The machine is turned on and the DC main relay is closed for 400ms | Warning‘AC1-10 bus overvoltage', the AC module is turned off, triggering AC fault record , and the history Warning record is automatically entered after the fault disappears | 1. Check whether the positive and negative bus calibration is corrected; 2. Check whether there is any problem with the N-row connection method for multi-branch models; 3. No transformer may also cause the fault |
Ac relay short circuit | AC soft start relay is not closed && AC main relay is not closed && module is not turned on && Inverter line voltage has at least one > 24% of rated voltage | Warning‘AC1-10 AC relay short circuit, the AC module is turned off, triggering AC fault record, can be manually cleared, and the history Warning record is automatically entered after the fault disappears | 1. Check whether the internal AC relay of the module is stuck or short-circuited, repair or replace the module |
Synchronous signal fault 2 | The carrier bus cannot detect the descending edge for 20ms | Warning‘AC1-10 synchronous signal fault 2', the AC module is turned off, and the history Warning record is automatically entered after the fault disappears | Check whether the module communication terminal is firmly connected, and then power on to check again; Replace the module |
Microgrid battery energy is low | When DC module power supply number >0, AC module ID> module power supply number Warning shutdown OR DC fault requires closing AC, AC is off-grid mode OR The rack is off-grid and receives the U2 control battery voltage low shutdown command | Warning‘AC1-10 microgrid battery energy is low',the AC module is turned off, triggering AC fault record , and the history Warning record is automatically entered after the fault disappears. | The number of DC modules shall not be less than the number of AC modules |
Grid phase-locking failed | In the grid-tied mode, phase lock fault (>10°) | Warning‘AC1-10 grid phase-locking failed', the AC module is turned off, triggering AC fault record , and the history Warning record is automatically entered after the fault disappears |