First time start
PWS1 series, grid-tied
- Make sure all settings about battery are properly set.
- On page “ctrl mode”, make sure it’s set to “Local Manual”
- On page “settings-Sys”, make sure it’s set to “on-grid”(or it can be “on” below “clear faults” in some old version)
- On page “settings-AC”, you can set the “Power configuration”, fill it with your target power, the unit is kW. A minus number is discharging, while a positive number is charging.
- On page “On/Off”, press “Sys ON”
PWS2-30K, grid-tied
- Make sure all settings about battery are properly set.
- On page “settings”, if you see “Ctrl mode remote” change it to “local”
- On page “controls”, toggle to the second page, make sure it’s set to “ON-GRID”
- On page “controls”, toggle to the third page, set the “Active power” to your target power, the unit is kW. minus value indicates charging, positive value indicates discharging.
- On page “controls”, toggle to the first page, press “ON”.