This is an old revision of the document!
Select DC dispatch or AC dispatch
Sinexcel PCS supports DC dispatch and AC dispatch
What is DC dispatch and AC dispatch
An inverter is a bi-port network, it has two ports, DC and AC. In theory, the AC power equals to DC power, if there's no self consumption.
But actually, there is a efficiency issue. We have the following equtions
In Charging $$P_{DC}=P_{AC}\times \eta _{charge}$$ In Discharging $$P_{AC}=P_{DC}\times \eta _{discharge}$$
Once one of $P_{DC}$ and $P_{AC}$ is designated, the other one is determined.
Depending on the designated port, there is AC dispatching mode and DC dispatching mode
AC dispatch
In AC dispatch mode,
You can
- designate AC active power (total, but NOT each string for multi-string version)
- designate AC reactive power
- activate P-PF, Volt-VAr, Freq-Watt, Volt-Watt
You can NOT
- designate DC power
- designate DC current
String dispatch
String dispatch mode is kind of AC dispatching for multi-string PCS,
You can
- designate AC active power of each string for multi-string version, but NOT total power
- designate AC reactive power in total (total, but not each string for multi-string version)
- activate P-PF, Volt-VAr, Freq-Watt, Volt-Watt
You can NOT
- designate DC power
- nor designate DC current
DC dispatch
In DC dispatch mode,
You can
- designate DC power but not DC current (of each string for multi-string version)
- or designate DC current but not DC power (of each string for multi-string version)
You can NOT
- designate AC active power
- designate AC reactive power
- activate P-PF, Volt-VAr, Freq-Watt, Volt-Watt