This is an old revision of the document!
Settings on the HMI
HMI settings
System RTC
To set the real time clock
System
Starting method
- Manually
- the PCS will NOT start until started manually or remotely. - Auto start after powered
- the PCS will start after powered up.
Energy dispatching mode
there are 2 options
- AC dispatch
- String dispatch
- DC dispatch
Refer to DC dispatch and AC dispatch for more information
In most applications, select AC dispatch.
For multi-string models, select String dispatch.
rarely, DC dispatch is supposed to be selected.
AC
This menu contains all parameters that affects the performance of the AC side of the PCS. Note that depending on the mode selected, the AC side parameters may not take effect, or may not be settable
Reactive power regulation mode
There are 3 modes supported in regulating reactive power
- Constant reactive power
- the reactive power will be designated by reactive power setpoint directly - Volt-VAr
- the reactive power will be designated by the grid voltage, following the curve made by several Volt-VAr (V,Q) points
PF setpoint
This setpoint will take effect ONLY when Reactive power regulation mode is set to Constant PF
Active power setpoint
To regulate the importing and exporting active power of the PCS, MUST be the most important setpoint in PCS
Rective power setpoint
This setpoint will take effect ONLY when Reactive power regulation mode is set to Constant reactive power
Smart Inverter function - Normal ramp rate (RR)
If Power change mode is set to ramp, in normal operation, the power setpoint changes, the actual import/export power will slowly change with this slope setpoint.
Smart Inverter function - Soft-Start ramp rate (SS)
AKA Connect/Reconnect Ramp-up rate Upon starting to inject power into the grid, following a period of inactivity or a disconnection, the inverter will be able to control its rate of increase of power from 1 to 100% maximum current per second.
Smart Inverter function - Grid reconnect delay
Following a trip, the Smart Inverter must delay re-energization or reconnection for a preset period of time once the voltage and frequency of the grid are within normal ranges.
Off-grid voltage regulation
This setpoint will tune the off-grid voltage within the range of ±10% of the the rated AC voltage.
Active power regulation mode
there are 3 modes supported in regulating active power
- Constant active power
- the active power will be designated by the active power setpoint directly - Freq-Watt
- the active power will be designated by the active power setpoint when frequency is in normal range, once the frequency rises beyond the range, the active power will reduce with the Freq-Watt slope - Volt-Watt
- the active power will be designated by the active power setpoint when voltage is in normal range, once the voltage rises beyond the range, the active power will reduce with the Volt-Watt slope - Freq-Watt and Volt-Watt
- the active power will be designated by the active power setpoint when both frequency or voltage is in normal range, once the voltage or frequency rises beyond the range, the active power will reduce with the Frequency-Watt and Volt-Watt slope, but frequency will be priory.
Power change mode
there are 2 modes
- Step
- the power will change instantly when setpoint is changed, suitable for applications such as frequency regulation - Ramp
- the power will change linearly with the normal ramp rate when setpoint is changed.
Smart Inverter function - F/VRT
Disable or enable F/VRT (Frequency Ride-through and Voltage Ride-through) functions
Smart Inverter function - Anti-islanding
By enabling this option, the anti-islanding function will be activated
Off-grid power starting
There are 2 options
- Step
- the PCS will generate the AC voltage instantly when it's started - Soft-Start
- when it's started, the PCS will close AC relays, and then generate the AC voltage slowly, to avoid potential inrush current. If the PCS trips after off-grid starting, worth a try on this option.
DC
This menu contains all parameters that affects the performance of the DC side of the PCS. Note that depending on the mode selected, the DC side parameters may not take effect, or may not be settable
Subsystem
The Sinexcel PCS are classed with different types
- Standard one string, which has only one DC string
- Multi-string, which has multiple DC strings, mostly one module is connected to one battery string
We call each string subsystem.
DC operation mode
there are 2 modes in this option
- Constant power
the PCS will import/export designated DC power, ignoring the AC power setpoints - Constant current
the PCS will import/export designated DC current if SOC supports, ignoring the AC power setpoints
both of the two options take effect ONLY when Energy dispatching mode is set to DC dispatch
Dis-/charge current setpoint
The PCS will import/export the power at DC side, according to this setpoint This setpoint takes effect ONLY when Energy dispatching mode is set to DC dispatch, and DC operation mode is set to Constant current
Dis-/charge power setpoint
The PCS will import/export the power at DC side, according to this setpoint This setpoint takes effect ONLY when Energy dispatching mode is set to DC dispatch, and DC operation mode is set to Constant power
Lower limit voltage of battery
This is the secondary under-voltage criterion. If the voltage reaches this threshold, it's critical for the ESS. the EMS must consider charging the battery at this moment.
Usually this threshold should be set 5~10V lower than end of discharge voltage
Float charge voltage
A legacy setpoint for lead-acid battery. If you are using lithium-ion battery, this setpoint MUST be the same as topping charge voltage
Topping charge voltage
refer to this article battery_dis-_charge_sequence
For lithium ion batteries, the PCS will stop charging the battery when the DC voltage reaches topping charge voltage, AND the DC current reduces to end of charge current
Max. charge current (DC)
The battery charging current (DC) will never be more than this threshold
Max. discharge current (DC)
The battery discharging current (DC) will never be more than this threshold
Start of discharge voltage
End of discharge voltage
if the PCS is discharging, once the voltage reaches this criteria, the PCS will stop and refuse to discharge.
Precharge voltage (legacy)
A legacy setpoint for lead-acid battery. If you are using lithium-ion battery, ignore this option
Precharge time (legacy)
Another legacy setpoint for lead-acid battery. If you are using lithium-ion battery, ignore this option
End of charge current
When the battery is charged as the voltage is almost reaching topping charge voltage, the current will reduce. Once the current drops to this threshold, the PCS will stop charging the battery.