definition:clear_fault_flag

Clear fault flag

When fault occurs, the Sinexcel inverter will stop operation with fault reporting. In this case, the Sinexcel inverter will not response to a start command before fault flag is cleared.

If the EMS finds that the Sinexcel inverter is in fault, the first thing is sending a stop regardless of the Sinexcel inverter status. Then several clear fault commands shall be sent to ensure it is not a fake fault.

If the Sinexcel inverter cannot jump to standby mode after several clear fault commands, it means that something serious really happened.

It’s recommended that the EMS sends a fault clear command every time before sending a start command, in case of there being a fault.