First time start

PWS1 series, grid-tied

  1. Make sure all settings about battery are properly set.You must know the operating password.
  2. On page ctrl mode, make sure it’s set to Local Manual
  3. On page settings-Sys, make sure it’s set to on-grid(or it can be on below clear faults in some legacy version)
  4. On page settings-AC, you can set the Power configuration, fill it with your target power, the unit is kW. A minus number is discharging, while a positive number is charging.
  5. On page On/Off, press Sys ON

PWS2-30K, grid-tied

  1. Make sure all settings about battery are properly set. You must know the operating password.
  2. On page settings, if you see ctrl mode: remote, change it to “local”
  3. Back to the main menu.
  4. On page controls, toggle to the second page, make sure it’s set to ON-GRID
  5. On page controls, toggle to the third page, set the Active power to your target power, the unit is kW. Minus value indicates charging, positive value indicates discharging.
  6. On page controls, toggle to the first page, press ON.
  7. You can regulate the target power when the PWS2-30K is ON

PWG2 series, PV+ Storage

to be filled