====== Communication connection ======
===== Bottom view=====
{{:manual:pws2-30k:微信图片_20220321142840.png?600|}}
^No. ^Description^
|1 |DC waterproof tube + |
|2 |DC waterproof tube - |
|3 |Ethernet waterproof terminal |
|4 |RS-485 waterproof terminal |
|5 |R-EPO waterproof terminal|
|6 |AC waterproof tube|
|7 |AC disconnect|
|8 |Fan box|
PWS2-30K-NA has two different communication interfaces: Ethernet and RS-485, meanwhile, there is a remote emergency power off terminal.
At the same time, the PWS2-30K-NA can only be configured to communicate with the EMS via Ethernet, or RS-485, refer to HMI operation for more information
===== Ethernet cable connection =====
PWS2-30K-NA can be directly controlled through Ethernet for remote control. Through networking, users can remote dispatch energy, monitor operation status, and set parameters with MODBUS TCP/IP protocol.
{{:manual:pws2-30k:image139_ethernet_cable.png|}}
The pinout of a standard T-568B straight-through ethernet cable:
^Pin^Color^
|1|white/orange|
|2|Orange|
|3|white/green|
|4|blue|
|5|white/blue|
|6|green|
|7|white/brown|
|8|brown|
- Penetrate network cable whose insulating layer is stripped into the waterproof cap and insert it into RJ45 connector after being arranged in order;
- Use wire crimpers to compress the connector;
- Screw out the cap on the waterproof Ethernet terminal at the bottom of the inverter;
- Insert the ready-made cable into Ethernet terminal.
====== RS-485 cable connection ======
PWS2-30K-NA can be connected to EMS through RS-485 to obtain battery information and energy dispatching command and complete automatic charging and discharging control and protection of energy storage system. RS-485 is connected through RJ45 connector. The definition of the pin of RJ45 connector is shown in the following image. The connection steps are the same as Ethernet cable.
{{:manual:pws2-30k:image140_rs485_cable.png|}}
====== Remote EPO connection ======
A remote EPO switch can be connected to the R-EPO RJ45 port.
{{:manual:pws2-30k:image142_emergency_power_off.png|}}
THE R-EPO IS A NORMAL CLOSED CONTACT. IT SHOULD BE CONNCTED TO A NC SWITCH OR BUTTON.
IF NO REMOTE EPO IS NEEDED, PLEASE DISABLE THE EPO FUNCTION IN HMI.