product_specification:pws2-30k-na

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Next revision
Previous revision
product_specification:pws2-30k-na [2018/12/26 03:38]
admin created
product_specification:pws2-30k-na [2020/09/16 21:42] (current)
Line 1: Line 1:
 ====== PWS2-30K-NA ====== ====== PWS2-30K-NA ======
-^ Item           ^ Heading 3          ^ + 
-| Row 1 Col 1    | Row 1 Col 2      +<WRAP center round download 60%> 
-| Row 2 Col 1    | some colspan | +{{ :product_specification:pws2-30k-na.pdf |Spec sheet}} 
-| Row 3 Col 1    | Row 3 Col 2     |  +</WRAP> 
-^Utility-interactive Mode^^ +<WRAP center round download 60%> 
-|Battery charge/discharge voltage |200V~750V (350~750V Full Power)+{{ :product_specification:pws2-30k-na_single_phase.pdf |Spec sheet (Single-phase)}} 
-|Battery charge/discharge current |90A Max| +</WRAP
-|AC voltage| 480V(423V~528V)| + 
-|AC current 36A| +<WRAP center round download 60%> 
-|Nominal power 30kW| +{{ :product_specification:170104052gzu-001_atm.pdf |ETL certificate}} 
-|AC frequency 60Hz(59.5Hz~60.5Hz) +</WRAP> 
-|AC PF| Listed0.8~1 leading or lagging (Controllable) + 
-|Actual0.1~1 leading or lagging (Controllable) +<WRAP center round download 60%> 
-Stand-alone Mode  +{{ :product_specification:pws2-30k-na_3d.zip |3D model (step format)}} 
-Battery discharge voltage 200V~750V (350~750V Full Power) +</WRAP> 
-Battery discharge current 90A Max + 
-AC output voltage 480V(±5% configurable) +
-AC output current 36A +
-Nominal AC output power 30kW(33kW max) +
-AC frequency 60Hz +
-AC output PF Listed: 0.8~1 leading or lagging (Load-depend) +
-Actual: 0.1~1 leading or lagging (Load-depend+
-Overload Capability 105%~115%  10min; +
-115%~125%  1min; +
-125%~150%  200ms +
-Physical  +
-Cooling Forced air cooling with replaceable fan module +
-Noise <65dB +
-Enclosure IP32/NEMA1 +
-Max elevation 3000m/10000feet (2000m/6500feet derating) +
-Operating temp. -20°C to 60°C (De-rating over 45°C) +
-Humidity 0~95(No condensing) +
-Size (W*H*D) 470*660*176mm/ +
-18.5*26*6.95 inches +
-Weight 43kg/95Lbs +
-Installation Wall-mounted +
-Other  +
-Peak efficiency 97.3+
-CEC efficiency 96.5% +
-Protection OTP, AC OVP/UVP, OFP/UFP, EPO, AC Phase Reverse, Fan/Relay Failure, OLP, GFDI, Anti-islanding +
-Configurable protection limits Upper/Lower AC Voltage/Frequency limit, Battery EOD voltage. +
-AC connection 3-Phase+N+PE +
-240V Split-phase (extra transformer required, derated to 17.3kW+
-Isolation Non-isolation +
-Certification ETL listed conforming to UL1741/UL1741SA, CPUC RULE 21, IEEE1547 +
-Short circuit  +
-Peak short circuit current 62A@20ms +
-Initial value of aperiodic current 62A@100ms +
-Initial symmetrical short circuit current 54A@250ms +
-Decaying component of short circuit current 54A@500ms +
-Time to trip 119ms+
  