Line 1: Line 1:
-====== PWS1-50K-NA ====== +====== PWS1-50K-NA PWS1-100K-NA PWS1-150K-NA PWS1-250K-NA ======
-^Model^PWS1-50K-NA^PWS1-100K-NA^PWS1-150K-NA^PWS1-250K-NA+
-^Utility-interactive Mode^^^^^ +
-|Battery dis-/charge voltage| 500V~850V |||| +
-|Battery dis-/charge current|0~110A|0~220A|0~330A|0~550A| +
-|AC voltage| 480V(423V~528V) |||| +
-|AC current|60A|120A|180A|300A| +
-|Nominal power|50kVA|100kVA|150kVA|250kVA| +
-|AC frequency| 60Hz(59.5Hz~60.5Hz) |||| +
-|AC PF| Listed: 0.8~1 leading or lagging (Controllable)\\ Actual: 0.1~1 leading or lagging (Controllable) |||| +
-^Stand-alone Mode^^^^^ +
-|Battery discharge voltage| 500V~850V |||| +
-|Battery discharge current| 0~110A | 0~220A | 0~330A | 0~550A | +
-|AC output voltage| 480V(±5% configurable) |||| +
-|AC output current|60A|120A|180A|300A| +
-|Nominal AC output power| 50kVA (55kVA max) |||| +
-|AC frequency| 60Hz |||| +
-|AC output PF|Listed: 0.8~1 leading or lagging (Load-depend)\\ Actual: 0.1~1 leading or lagging (Load-depend)|||| +
-|Overload Capability|105%~115% 10min;\\ 115%~125% 1min;\\ 125%~150% 200ms|||| +
-^Physical^^ +
-|Cooling| Forced air cooling |||| +
-|Noise| <65dB |||| +
-|Enclosure| IP20/NEMA1 |||| +
-|Max elevation| 3000m/10000feet (> 2000m/6500feet derating) |||| +
-|Operating temperature| -20°C to 60°C (De-rating over 45°C)|||| +
-|Humidity| 0~95% (No condensing) |||| +
-|Size (W*H*D)| 800*2160*800mm ||| 1200*2160*800mm | +
-|Weight|465kg|||| +
-|Installation| Floor standing |||| +
-^Other^^^^^ +
-|Peak efficiency| 95.5% |||| +
-|CEC efficiency| 94% |||| +
-|Protection|Over temperature,\\ AC over/under current,\\ AC over/under frequency,\\ EPO,\\ AC phase reversion,\\ Fan/relay failure,\\ Over load,\\ GFDI(AC),\\ Anti-islanding,\\ Configurable protection limits: Upper/lower AC voltage/frequency limit, battery EOD voltage.|||| +
-|AC connection| 3-Phase 4-wire |||| +
-|Isolation| internal transformer |||| +
-|Certification| ETL listed conforming to UL1741/UL1741SA, CPUC Rule 21, HECO Rule 14H, IEEE1547, HECO listed, CA listed|||| +
-^Short circuit^^^^^ +
-|Short circuit current| 200A | 400A | 600A | 1000A | +
-|Time to trip| 100ms ||||+
  
 +  * [[|Spec sheet]]
 +  * [[|Certificate]]
 +  * [[|Test report]]