-====== PWS2-50K-NA ====== +====== PWS1-50K-NA / PWS1-100K-NA PWS1-150K-NA PWS1-250K-NA ======
- +
-^Utility-interactive Mode^^ +
-|Battery dis-/charge voltage|500V~850V| +
-|Battery dis-/charge current|0~110A| +
-|AC voltage|480V(423V~528V)| +
-|AC current|60A| +
-|Nominal power|50kW| +
-|AC frequency|60Hz(59.5Hz~60.5Hz)| +
-|AC PF|Listed: 0.8~1 leading or lagging (Controllable)| +
-|:::|Actual: 0.1~1 leading or lagging (Controllable)| +
-^Stand-alone Mode^^ +
-|Battery discharge voltage|500V~850V| +
-|Battery discharge current|0~110A| +
-|AC output voltage|480V(±5% configurable)| +
-|AC output current|60A| +
-|Nominal AC output power|50kW (55kW max)| +
-|AC frequency|60Hz| +
-|AC output PF|Listed: 0.8~1 leading or lagging (Load-depend)| +
-|:::|Actual: 0.1~1 leading or lagging (Load-depend)| +
-|Overload Capability|105%~115% 10min;| +
-|:::|115%~125% 1min;| +
-|:::|125%~150% 200ms| +
-^Physical^^ +
-|Cooling|Forced air cooling| +
-|Noise|<65dB| +
-|Enclosure|IP20/NEMA1| +
-|Max elevation|3000m/10000feet (> 2000m/6500feet derating)| +
-|Operating temperature|-20°C to 60°C (De-rating over 45°C)| +
-|Humidity|0~95% (No condensing)| +
-|Size (W*H*D)|800*2160*800mm| +
-|Weight|465kg| +
-|Installation|Floor standing| +
-^Other^^ +
-|Peak efficiency|95.5%| +
-|CEC efficiency|94%| +
-|Protection|Over temperature,\\ AC over/under current,\\ AC over/under frequency,\\ EPO,\\ AC phase reversion,\\ Fan/relay failure,\\ Over load,\\ GFDI(AC),\\ Anti-islanding,\\ Configurable protection limits: Upper/lower AC voltage/frequency limit, battery EOD voltage.| +
-|AC connection|3-Phase+N+PE | +
-|Isolation|internal transformer| +
-|Certification|ETL listed conforming to UL1741/UL1741SA, CPUC Rule 21, HECO Rule 14H, IEEE1547| +
-^Short circuit^^ +
-|Short circuit current|200A| +
-|Time to trip|100ms|+
  
 +  * [[|Spec sheet]]
 +  * [[|Certificate]]
 +  * [[|Test report]]