manual:pws2-30k:manual_operation [2019/01/11 01:16] admin [Manually start in grid-tied mode] |
manual:pws2-30k:manual_operation [2020/09/16 22:16] (current) |
||
---|---|---|---|
Line 10: | Line 10: | ||
CB---CBA[AC] | CB---CBA[AC] | ||
CB---CBB[Battery] | CB---CBB[Battery] | ||
- | CB---CBC[Grapgh] | + | CB---CBC[Graph] |
C---CC[status] | C---CC[status] | ||
CC---CCA[Warnings] | CC---CCA[Warnings] | ||
Line 28: | Line 28: | ||
- | ===== Loading | + | ===== Loading ===== |
After system startup, it will automatically jump to home page. | After system startup, it will automatically jump to home page. | ||
Line 59: | Line 59: | ||
===== Energy ===== | ===== Energy ===== | ||
- | Click Energy in the main interface to enter the display of energy. Users can read AC, Battery, PV, Switches and Graph information | + | Click **Energy** in the main interface to enter the display of energy. Users can read AC, Battery, PV, Switches and Graph information |
==== AC information ==== | ==== AC information ==== | ||
- | Click Energy to enter the display of AC information (or click AC in the left side to enter), < and > under the interface to turn page up or down, click | + | Click **Energy** to enter the display of AC information (or click AC in the left side to enter), |
^Item ^Identifier ^Description ^Unit^ | ^Item ^Identifier ^Description ^Unit^ | ||
- | |Voltage |Uab, | + | |Voltage |Uab, |
|Current |Ia, | |Current |Ia, | ||
|Active power |P |Active power of AC of inverter |kW| | |Active power |P |Active power of AC of inverter |kW| | ||
Line 84: | Line 84: | ||
==== Battery information ==== | ==== Battery information ==== | ||
- | Click Batt. in the left side to enter, < and > under the interface to turn page up or down, click | + | Click **Batt.** in the left side to enter, |
- | ^Battery information | + | ^Battery information^Item ^Identifier ^Description ^Unit ^ |
- | ^Item ^Identifier ^Description ^Unit ^ | + | |
|Power |P |Real-time power of battery charging and discharging |kW| | |Power |P |Real-time power of battery charging and discharging |kW| | ||
|Voltage |U |Voltage of DC output port of inverter |V| | |Voltage |U |Voltage of DC output port of inverter |V| | ||
Line 101: | Line 100: | ||
==== Graph display ==== | ==== Graph display ==== | ||
- | Click Graph in the left side to enter the graph display. This interface can display the curve for charging and discharging power of inverter in current day. Click to return the main menu. | + | Click **Graph** in the left side to enter the graph display. This interface can display the curve for charging and discharging power of inverter in current day. click {{: |
{{: | {{: | ||
===== Records ===== | ===== Records ===== | ||
- | Click Status in the main interface to search current warning, historical warning and logs. Click Status to enter the current warning interface. As for other interfaces in this function, click Warnings to enter. This interface includes three columns: “number”, | + | Click **Status** in the main interface to search current warning, historical warning and logs. Click Status to enter the current warning interface. As for other interfaces in this function, click Warnings to enter. This interface includes three columns: “number”, |
{{: | {{: | ||
- | Click Historical Warnings to enter the historical warning interface. This interface includes three columns: “number”, | + | Click **Historical Warnings** to enter the historical warning interface. This interface includes three columns: “number”, |
{{: | {{: | ||
+ | <WRAP center round tip 60%> | ||
If the inverter is restarted or shut down due to power failure, the warning will still exist. After being powered on, the end time of warning will be expressed as “--/ | If the inverter is restarted or shut down due to power failure, the warning will still exist. After being powered on, the end time of warning will be expressed as “--/ | ||
+ | </ | ||
- | Click Logs to enter the operation logs interface. This interface includes three columns: “number”, | + | Click **Logs** to enter the operation logs interface. This interface includes three columns: “number”, |
{{: | {{: | ||
Line 121: | Line 122: | ||
===== Control parameter ===== | ===== Control parameter ===== | ||
- | Click Controls to enter the control interface of convert operation state. This interface includes grid-tied and off-grid control, startup and shutdown control and output power setting. Click Controls to enter “startup and shutdown” operation interface to manually start and shut down the inverter. This interface includes Clear Faults button which used to clear some fault signals which must be cleared manually. After parameter setting is completed and startup conditions are met, the inverter can be started and shut down by ON and OFF buttons. | + | Click **Controls** to enter the control interface of convert operation state. This interface includes grid-tied and off-grid control, startup and shutdown control and output power setting. Click **Controls** to enter “startup and shutdown” operation interface to manually start and shut down the inverter. This interface includes Clear Faults button which used to clear some fault signals which must be cleared manually. After parameter setting is completed and startup conditions are met, the inverter can be started and shut down by ON and OFF buttons. |
{{: | {{: | ||
- | Click > under the interface to turn page up to enter the inverter grid-tied and off-grid control interface. PWS2-30K-NA energy storage inverter can operate in grid-tied mode and off-grid mode. During grid-tied operation, close the isolator S2 in AC and the breaker D3 (the breaker between the inverter and the power grid.), and set the energy storage inverter in grid-tied mode through the operation interface. During off-grid operation, close the isolator S2 in AC and the AC breaker D3, turn off the AC breaker of intelligent power distribution cabinet, and set the energy storage inverter into off-grid mode. | + | Click **>** under the interface to turn page up to enter the inverter grid-tied and off-grid control interface. PWS2-30K-NA energy storage inverter can operate in grid-tied mode and off-grid mode. During grid-tied operation, close the isolator S2 in AC and the breaker D3 (the breaker between the inverter and the power grid.), and set the energy storage inverter in grid-tied mode through the operation interface. During off-grid operation, close the isolator S2 in AC and the AC breaker D3, turn off the AC breaker of intelligent power distribution cabinet, and set the energy storage inverter into off-grid mode. |
{{: | {{: | ||
- | Click > under the interface to turn page down (or click < in “startup and shutdown” interface) to return the operation interface of “output power”. Output power can be controlled manually. | + | Click **>** under the interface to turn page down (or click **<** in “startup and shutdown” interface) to return the operation interface of “output power”. Output power can be controlled manually. |
Control page of electric power parameters | Control page of electric power parameters | ||
^Item ^Identifier ^Application scenarios ^Description^ | ^Item ^Identifier ^Application scenarios ^Description^ | ||
- | |Output voltage amplitude regulation |Vol. Regulation | + | |Output voltage amplitude regulation |Vol. Regulation |
|Output voltage frequency regulation |Freq. Regulation |Off-grid mode|Regulate the output voltage frequency in off-grid mode. Regulated range ±1Hz| | |Output voltage frequency regulation |Freq. Regulation |Off-grid mode|Regulate the output voltage frequency in off-grid mode. Regulated range ±1Hz| | ||
|Active power regulation |Active Power |Grid-tied mode |Regulate the active power of AC in grid-tied mode. Regulated range ±30kW| | |Active power regulation |Active Power |Grid-tied mode |Regulate the active power of AC in grid-tied mode. Regulated range ±30kW| | ||
Line 139: | Line 140: | ||
+ | <WRAP center round important 60%> | ||
When the dispatched apparent power exceeds 30kVA, the output of active power will be restricted by reactive power, and the system will give priority to reactive output. | When the dispatched apparent power exceeds 30kVA, the output of active power will be restricted by reactive power, and the system will give priority to reactive output. | ||
+ | </ | ||
<WRAP center round important 60%> | <WRAP center round important 60%> | ||
Line 150: | Line 153: | ||
===== Settings ===== | ===== Settings ===== | ||
- | Click Settings to enter the system operation parameter setting which includes Battery, HMI, Debug and Hardware parameter setting. | + | Click **Settings** to enter the system operation parameter setting which includes Battery, HMI, Debug and Hardware parameter setting. |
| | ||
The initial password is 123456 | The initial password is 123456 | ||
Line 156: | Line 159: | ||
==== battery parameters ==== | ==== battery parameters ==== | ||
- | Click Battery to enter battery charging and discharging parameter setting. Click < and > under the interface to turn page down, and click | + | Click **Battery** to enter battery charging and discharging parameter setting. Click **<** and **>** under the interface to turn page down, and click {{: |
{{: | {{: | ||
Line 181: | Line 184: | ||
==== HMI parameters ==== | ==== HMI parameters ==== | ||
- | Click HMI to enter monitoring parameter setting, as shown in Fig. 5 15. Click < and > under the interface to turn page down, and click | + | Click **HMI** to enter monitoring parameter setting. Click **<** and **>** under the interface to turn page down, and click {{: |
{{: | {{: | ||
Line 210: | Line 213: | ||
<WRAP center round important 60%> | <WRAP center round important 60%> | ||
- | Before clicking | + | Before clicking |
- | After clicking | + | After clicking |
</ | </ | ||
+ | <WRAP center round important 60%> | ||
When control mode is set as remote, all manual controls are disabled. | When control mode is set as remote, all manual controls are disabled. | ||
- | When control mode is set as manual, all remote controls are disabled. | ||
+ | When control mode is set as manual, all remote controls are disabled. | ||
+ | </ | ||
==== Debug interface ==== | ==== Debug interface ==== | ||
- | Click Debug to enter debugging interface, and click < and > under the interface to turn page down, and click | + | Click **Debug** to enter debugging interface, and click **<** and **>** under the interface to turn page down, and click {{: |
<WRAP center round warning 60%> | <WRAP center round warning 60%> | ||
| | ||
Line 227: | Line 231: | ||
==== Hardware parameters ==== | ==== Hardware parameters ==== | ||
- | Click Hardware to enter hardware parameter setting, and click | + | Click **Hardware** to enter hardware parameter setting, and click {{: |
<WRAP center round warning 60%> | <WRAP center round warning 60%> | ||
- | | + | |
+ | Users can review hardware information in this interface, but they cannot set the parameters. Any loss arising from customers’ modifying the parameters in this interface will be undertaken by customers. | ||
</ | </ | ||
Line 235: | Line 240: | ||
==== Inverter information ==== | ==== Inverter information ==== | ||
- | Click About to enter the inverter information interface, as shown in Fig. 5 16. Click to return the main menu. This interface includes inverter serial number, MAC address, software build number, grid status and the rated power of the inverter. | + | Click **About** to enter the inverter information interface. |
{{: | {{: |