manual:pws2-30k:electrical_connection

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revision Previous revision
Next revision
Previous revision
manual:pws2-30k:electrical_connection [2019/01/03 03:35]
admin
manual:pws2-30k:electrical_connection [2022/03/21 03:23] (current)
hedy [Bottom view]
Line 2: Line 2:
 PWS2-30K-NA electrical wiring should strictly following the following requirements. Please read the following carefully.  PWS2-30K-NA electrical wiring should strictly following the following requirements. Please read the following carefully. 
 <WRAP center round danger 60%> <WRAP center round danger 60%>
- **DANGER**\\ Before electrical connection, please ensure that all switches of energy storage system are in “OFF” state. Otherwise, the high voltage of the inverter might cause an electric shock risk. + **DANGER**\\ Before electrical connection, please ensure that all switches of energy storage system are in “OFF” . Otherwise, the high voltage of the inverter might cause an electric shock risk. 
 </WRAP> </WRAP>
  
Line 14: Line 14:
  **CAUTION**\\ The cable colors mentioned in all electrical connection diagrams in this chapter are for reference only. Cable selection should comply with local cable standard.   **CAUTION**\\ The cable colors mentioned in all electrical connection diagrams in this chapter are for reference only. Cable selection should comply with local cable standard. 
 </WRAP> </WRAP>
 +
 +===== Bottom view=====
 +{{:manual:pws2-30k:微信图片_20220321142840.png?600|}}
 +^No. ^Description^
 +|1 |DC waterproof tube + |
 +|2 |DC waterproof tube - |
 +|3 |Ethernet waterproof terminal |
 +|4 |RS-485 waterproof terminal |
 +|5 |R-EPO waterproof terminal|
 +|6 |AC waterproof tube|
 +|7 |AC disconnect|
 +|8 |Fan box|
 +
 +=====  Bottom cover removal =====
 +
 +To ensure electric safety, the electric wiring terminal of the case is closely blocked by the bottom cover. Before wiring, remove the bottom cover.\\ 
 +{{:manual:pws2-30k:image134_remove_bottom_cover.png|}}
 +
 +===== Power terminals =====
 +The power terminals of PWS2-30K is shown in the image below. 
 +
 +The cable colors, grounding, wiring should consist to the local electrical code. 
 +
 +{{:manual:pws2-30k:image138_cable_installation.png|}}
 +
 +The recommended cable size:
 +  * Line: AWG 8
 +  * Neutral: AWG 8
 +  * PE: AWG 8
 +  * DC: AWG 4 (better consult your battery manufacturer)
 +
 +
 +<WRAP center round tip 60%>
 +In some contries, such as United States, cables shall always be enclosed by conduits. In this case, the waterproof caps should be removed.
 +</WRAP>
 +
 +
 +=====  Bottom cover restore =====
 +After power cables installed properly, the bottom cover should be reinstalled.
 +
  
  
  • manual/pws2-30k/electrical_connection.1546504500.txt.gz
  • Last modified: 2020/09/16 22:08
  • (external edit)