Line 47: Line 47:
 It is recommended that the inverter should be grounded locally. For multiple PWS2-30M-EX parallel connection system, the grounding points of all inverters should be connected with each other so as to ensure equal potential connection of grounding wires.  It is recommended that the inverter should be grounded locally. For multiple PWS2-30M-EX parallel connection system, the grounding points of all inverters should be connected with each other so as to ensure equal potential connection of grounding wires. 
 </WRAP> </WRAP>
-Step 1: Use a wire stripper to strip the insulating layer of the grounding wire in a proper length;  +Step 1: Use a wire stripper to strip the insulating layer of the grounding wire in a proper length; \\  
-Step 2: Penetrate the wire core whose insulating layer is stripped into the conductor crimping area of ring terminal. Press the ring terminal with a hydraulic clamp. +Step 2: Penetrate the wire core whose insulating layer is stripped into the conductor crimping area of ring terminal. Press the ring terminal with a hydraulic clamp. \\
 Step 3: Cover the terminal on the grounding bolt and screw up the nut. Step 3: Cover the terminal on the grounding bolt and screw up the nut.
  
Line 54: Line 54:
  
 ===== DC wiring ===== ===== DC wiring =====
-Specifications of cable and terminal:  +Specifications of cable and terminal: \\  
-  Grounding wire: the recommended cross-sectional area=25mm2 (3AWG) outdoor copper core cable +  Grounding wire: the recommended cross-sectional area=25mm2 (3AWG) outdoor copper core cable\\  
-  Ring terminal: M8 +  Ring terminal: M8\\  
-Step 1: Use a multi-meter to measure the voltage of battery and ensure that the voltage is within input voltage range of energy storage inverter. +Step 1: Use a multi-meter to measure the voltage of battery and ensure that the voltage is within input voltage range of energy storage inverter.\\  
-Step 2: Turn off the DC breaker. Wiring operation can be conducted after using a multi-meter to measure and confirm that there is no voltage between positive and negative poles of DC input. +Step 2: Turn off the DC breaker. Wiring operation can be conducted after using a multi-meter to measure and confirm that there is no voltage between positive and negative poles of DC input.\\  
-Step 3: Use a wire stripper to strip the DC cable in a proper length, cover a cord end terminal and use wire crimpers to compress it. Recommended DC cable 25mm2 (AWG 3) with copper cord.  +Step 3: Use a wire stripper to strip the DC cable in a proper length, cover a cord end terminal and use wire crimpers to compress it. Recommended DC cable 25mm2 (AWG 3) with copper cord. \\  
-Step 4: Connect the positive cable of the battery pack to the “DC+” of the DC terminal block so that the angle between the cable and the terminal block is 90 degrees. +Step 4: Connect the positive cable of the battery pack to the “DC+” of the DC terminal block so that the angle between the cable and the terminal block is 90 degrees.\\  
-Step 5: Connect the negative cable of the battery pack to the “DC-” of the DC terminal block so that the angle between the cable and the terminal block is 90 degrees. +Step 5: Connect the negative cable of the battery pack to the “DC-” of the DC terminal block so that the angle between the cable and the terminal block is 90 degrees.\\  
-Step 6: Confirm wiring firmness and lock of DC cable. +Step 6: Confirm wiring firmness and lock of DC cable. \\
 Remark: The angle of 90 degrees between the cable and the terminal is for convenient installation of the DC side protective case. Remark: The angle of 90 degrees between the cable and the terminal is for convenient installation of the DC side protective case.
  
Line 78: Line 78:
  
 ===== AC wiring ===== ===== AC wiring =====
-Step 1: Use a phase-sequence meter for measurement, and ensure that the phase consequence of wires should be correct. +Step 1: Use a phase-sequence meter for measurement, and ensure that the phase consequence of wires should be correct.\\  
-Step 2: Turn off the AC breaker connected to energy storage inverter. +Step 2: Turn off the AC breaker connected to energy storage inverter.\\  
-Step 3: Use a multi-meter to measure and confirm that the cables connected to the terminals are electrically neutral. +Step 3: Use a multi-meter to measure and confirm that the cables connected to the terminals are electrically neutral.\\  
-Step 4: Use a wire stripper to strip the AC cable in a proper length, cover a cord end terminal and use wire crimpers to compress it. Recommended AC cable 16mm2 (AWG 5) with copper cord.  +Step 4: Use a wire stripper to strip the AC cable in a proper length, cover a cord end terminal and use wire crimpers to compress it. Recommended AC cable 16mm2 (AWG 5) with copper cord. \\  
-Step 5: Connect AC cable to “L1”, “L2”, “L3” and “N” of AC wire terminal block; +Step 5: Connect AC cable to “L1”, “L2”, “L3” and “N” of AC wire terminal block;\\  
-Step 6: Confirm wiring firmness and lock the waterproof tube of AC cable.+Step 6: Confirm wiring firmness and lock the waterproof tube of AC cable.\\
  
 <WRAP center round warning 60%> <WRAP center round warning 60%>