* Since firmware D141, droop mode has been added to PWS2-30K/M, to provide a non-communication off-grid parallel operation solution. | * Since firmware D141, droop mode has been added to PWS2-30K/M, to provide a non-communication off-grid parallel operation solution. | ||
- | * Only 3-phase PWS2-30K/ | + | * Single |
===== To enable droop mode ===== | ===== To enable droop mode ===== | ||
* To write register 750(0x02EE) and 756(0x02F4), | * To write register 750(0x02EE) and 756(0x02F4), | ||
Line 26: | Line 26: | ||
* The droop mode will bring voltage and frequency fluctuation (90%~110%) | * The droop mode will bring voltage and frequency fluctuation (90%~110%) | ||
* The droop mode will bring some circulating current between each PWS2-30K/M, if the load is low in off-grid microgrid, the currents of each DC side of the PWS2-30K will be fluctuating not more than of ±5% | * The droop mode will bring some circulating current between each PWS2-30K/M, if the load is low in off-grid microgrid, the currents of each DC side of the PWS2-30K will be fluctuating not more than of ±5% | ||
- | * **If droop mode is enabled in grid-tied mode, there will be some unpredictable reactive power, DISABLE droop mode if it's not necessary for the grid-tied operation. | + | |
- | ** | + |