 ====== Droop mode precautions ====== ====== Droop mode precautions ======
 +<WRAP center round warning 60%>
 +Warning
 +
 +Droop control mode is still an experimental functionality, the performance depends.
 +</WRAP>
 +
 +
 +
 ===== Scope ===== ===== Scope =====
   * Since firmware D141, droop mode has been added to PWS2-30K/M, to provide a non-communication off-grid parallel operation solution.   * Since firmware D141, droop mode has been added to PWS2-30K/M, to provide a non-communication off-grid parallel operation solution.
-  * Only 3-phase PWS2-30K/supports droop mode, single phase firmware does NOT support droop mode yet.+  * Single phase firmware can supports three sets of inverters droop mode yet.
 ===== To enable droop mode ===== ===== To enable droop mode =====
-  * To write register 0x02EE and 0x02F4, authorization must be granted first, by writing 2007 to 0x0FA7 and 2016 to 0x0FA8. +  * To write register 750(0x02EEand 756(0x02F4), authorization must be granted first, by writing 2007 to register 4007(0x0FA7and 2016 to register 4008(0x0FA8)
-  * The PWS2-30K must be set to 3P3W, 0x02EE=1; and** NO neutral line connected** +  * The PWS2-30K must be set to 3P3W, 750(0x02EE)= 1; and** NO neutral line connected** 
-  * To enable droop mode, set 0x02F4=+  * To enable droop mode, set register 756(0x02F4) to 
-  * After enabling droop mode, a hard reboot is required.+  * After enabling droop mode, <del>a hard reboot is required.</del>, write 1 to register 657(0x0291) to reboot the software. make sure the inverter is not running at this moment. 
 ===== Requirements ===== ===== Requirements =====
   * A delta-wye transformer is required if 277V or 220V single phase load is required.   * A delta-wye transformer is required if 277V or 220V single phase load is required.
   * When multiple PWS2-30K/M are used for off-grid droop parallel operation, there must be one PWS2-30K establishing AC voltage first, and then the others can be started.   * When multiple PWS2-30K/M are used for off-grid droop parallel operation, there must be one PWS2-30K establishing AC voltage first, and then the others can be started.
-  * The maximum quantity of PWS2-30K/M for off-grid droop parallel operation in one microgrid is 9 units+  * The maximum quantity of PWS2-30K/verified to be working for off-grid droop parallel operation in one microgrid is 9 units (because we can only obtain 9 units in the lab)
   * When droop parallel operation implemented, the length of the cables from the PWS2-30K/M should be as same as possible.   * When droop parallel operation implemented, the length of the cables from the PWS2-30K/M should be as same as possible.
  
Line 17: Line 26:
   * The droop mode will bring voltage and frequency fluctuation (90%~110%)   * The droop mode will bring voltage and frequency fluctuation (90%~110%)
   * The droop mode will bring some circulating current between each PWS2-30K/M, if the load is low in off-grid microgrid, the currents of each DC side of the PWS2-30K will be fluctuating not more than of ±5%   * The droop mode will bring some circulating current between each PWS2-30K/M, if the load is low in off-grid microgrid, the currents of each DC side of the PWS2-30K will be fluctuating not more than of ±5%
-  * **If droop mode is enabled in grid-tied mode, there will be some unpredictable reactive power, DISABLE droop mode if it's not necessary for the grid-tied operaion. +
-**+