====== Droop mode precautions ====== | ====== Droop mode precautions ====== | ||
+ | <WRAP center round warning 60%> | ||
+ | Warning | ||
+ | |||
+ | Droop control mode is still an experimental functionality, | ||
+ | </ | ||
+ | |||
+ | |||
+ | |||
===== Scope ===== | ===== Scope ===== | ||
* Since firmware D141, droop mode has been added to PWS2-30K/M, to provide a non-communication off-grid parallel operation solution. | * Since firmware D141, droop mode has been added to PWS2-30K/M, to provide a non-communication off-grid parallel operation solution. | ||
- | * Only 3-phase PWS2-30K/ | + | * Single |
===== To enable droop mode ===== | ===== To enable droop mode ===== | ||
- | * To write register 0x02EE and 0x02F4, authorization must be granted first, by writing 2007 to 0x0FA7 and 2016 to 0x0FA8. | + | * To write register |
- | * The PWS2-30K must be set to 3P3W, 0x02EE=1; and** NO neutral line connected** | + | * The PWS2-30K must be set to 3P3W, 750(0x02EE)= 1; and** NO neutral line connected** |
- | * To enable droop mode, set 0x02F4=1 | + | * To enable droop mode, set register 756(0x02F4) to 1 |
- | * After enabling droop mode, a hard reboot is required. | + | * After enabling droop mode, <del>a hard reboot is required.</ |
===== Requirements ===== | ===== Requirements ===== | ||
* A delta-wye transformer is required if 277V or 220V single phase load is required. | * A delta-wye transformer is required if 277V or 220V single phase load is required. | ||
* When multiple PWS2-30K/M are used for off-grid droop parallel operation, there must be one PWS2-30K establishing AC voltage first, and then the others can be started. | * When multiple PWS2-30K/M are used for off-grid droop parallel operation, there must be one PWS2-30K establishing AC voltage first, and then the others can be started. | ||
- | * The maximum quantity of PWS2-30K/M for off-grid droop parallel operation in one microgrid is 9 units | + | * The maximum quantity of PWS2-30K/ |
* When droop parallel operation implemented, | * When droop parallel operation implemented, | ||
Line 17: | Line 26: | ||
* The droop mode will bring voltage and frequency fluctuation (90%~110%) | * The droop mode will bring voltage and frequency fluctuation (90%~110%) | ||
* The droop mode will bring some circulating current between each PWS2-30K/M, if the load is low in off-grid microgrid, the currents of each DC side of the PWS2-30K will be fluctuating not more than of ±5% | * The droop mode will bring some circulating current between each PWS2-30K/M, if the load is low in off-grid microgrid, the currents of each DC side of the PWS2-30K will be fluctuating not more than of ±5% | ||
- | * **If droop mode is enabled in grid-tied mode, there will be some unpredictable reactive power, DISABLE droop mode if it's not necessary for the grid-tied operaion. | + | |
- | ** | + |