manual:pws2-30k:communication_connection

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revision Previous revision
Next revision
Previous revision
manual:pws2-30k:communication_connection [2019/01/04 00:27]
admin
manual:pws2-30k:communication_connection [2022/03/21 03:16] (current)
hedy [Bottom view]
Line 1: Line 1:
 ====== Communication connection ====== ====== Communication connection ======
 +===== Bottom view=====
 +{{:manual:pws2-30k:微信图片_20220321142840.png?600|}}
 +^No. ^Description^
 +|1 |DC waterproof tube + |
 +|2 |DC waterproof tube - |
 +|3 |Ethernet waterproof terminal |
 +|4 |RS-485 waterproof terminal |
 +|5 |R-EPO waterproof terminal|
 +|6 |AC waterproof tube|
 +|7 |AC disconnect|
 +|8 |Fan box|
  
-PWS2-30K-NA has two different communication interfaces: Ethernet and RS-485. +PWS2-30K-NA has two different communication interfaces: Ethernet and RS-485, meanwhile, there is a remote emergency power off terminal. 
 + 
 +<WRAP center round tip 60%> 
 +At the same time, the PWS2-30K-NA can only be configured to communicate with the EMS via Ethernet, or RS-485, refer to HMI operation for more information 
 +</WRAP>
  
  ===== Ethernet cable connection =====  ===== Ethernet cable connection =====
Line 9: Line 24:
 {{:manual:pws2-30k:image139_ethernet_cable.png|}} {{:manual:pws2-30k:image139_ethernet_cable.png|}}
    
 +The pinout of a standard T-568B straight-through ethernet cable:
 +^Pin^Color^
 +|1|white/orange|
 +|2|Orange|
 +|3|white/green|
 +|4|blue|
 +|5|white/blue|
 +|6|green|
 +|7|white/brown|
 +|8|brown|
 +
   - Penetrate network cable whose insulating layer is stripped into the waterproof cap and insert it into RJ45 connector after being arranged in order;   - Penetrate network cable whose insulating layer is stripped into the waterproof cap and insert it into RJ45 connector after being arranged in order;
   - Use wire crimpers to compress the connector;    - Use wire crimpers to compress the connector; 
Line 16: Line 42:
 ====== RS-485 cable connection ====== ====== RS-485 cable connection ======
  
-PWS2-30K-NA can be connected to EMS through RS-485 to obtain battery information and energy dispatching command and complete automatic charging and discharging control and protection of energy storage system. RS-485 is connected through RJ45 connector. The definition of the pin of RJ45 connector is shown in Fig. 3 19. The connection steps are the same as Ethernet cable. +PWS2-30K-NA can be connected to EMS through RS-485 to obtain battery information and energy dispatching command and complete automatic charging and discharging control and protection of energy storage system. RS-485 is connected through RJ45 connector. The definition of the pin of RJ45 connector is shown in the following image. The connection steps are the same as Ethernet cable. 
  
 {{:manual:pws2-30k:image140_rs485_cable.png|}}  {{:manual:pws2-30k:image140_rs485_cable.png|}} 
- 
  
 ====== Remote EPO connection ====== ====== Remote EPO connection ======
Line 28: Line 53:
  
 <WRAP center round important 60%> <WRAP center round important 60%>
-THE R-EPO IS A NORMAL CLOSED CONTACT.IT SHOULD BE CONNCTED TO A NC SWITCH OR BUTTON.+THE R-EPO IS A NORMAL CLOSED CONTACT. IT SHOULD BE CONNCTED TO A NC SWITCH OR BUTTON.
 IF NO REMOTE EPO IS NEEDED, PLEASE DISABLE THE EPO FUNCTION IN HMI. IF NO REMOTE EPO IS NEEDED, PLEASE DISABLE THE EPO FUNCTION IN HMI.
 </WRAP> </WRAP>