Line 85: | Line 85: | ||
==== Volt-Watt | ==== Volt-Watt | ||
^Parameter on HMI (legacy name before M1330) | ^Parameter on HMI (legacy name before M1330) | ||
- | |Setting -> AC -> Page 8 -> Volt/Watt V1 |Volt-Watt V1 |1.06 (*480V) | | + | |Setting -> AC -> Page 8 -> Volt/Watt V1 |Volt-Watt V1 |1.06 (*480V) |1.06 (*480V) |1.06 (*480V) | |
|Setting -> AC -> Page 8 -> Volt/Watt ramp rate |useless, | |Setting -> AC -> Page 8 -> Volt/Watt ramp rate |useless, | ||
- | |Setting -> AC -> Page 8 -> Volt/Watt delay |Volt/ | + | |Setting -> AC -> Page 8 -> Volt/Watt delay |Volt/ |
- | |Setting -> AC -> Page 8 -> Volt/Watt V2 |Volt-Watt V2 |1.1 (*480V) | | + | |Setting -> AC -> Page 8 -> Volt/Watt V2 |Volt-Watt V2 |1.1 (*480V) |1.1 (*480V) |1.1 (*480V) | |
- | |Setting -> AC -> Page 8 -> Volt/Watt P1 |Volt-Watt P1 |1 (*power setpoint) | | + | |Setting -> AC -> Page 8 -> Volt/Watt P1 |Volt-Watt P1 |1 (*power setpoint) |1 (*power setpoint) |1 (*power setpoint) | |
- | |Setting -> AC -> Page 8 -> Volt/Watt P2 |Volt-Watt P2 |0 (*power setpoint) | | + | |Setting -> AC -> Page 8 -> Volt/Watt P2 |Volt-Watt P2 |0 (*power setpoint) |0 (*power setpoint) |0 (*power setpoint) | |
- | |Setting -> AC -> Page 8 -> Volt/Watt response time |Volt-Watt response time|10 s | | + | |Setting -> AC -> Page 8 -> Volt/Watt response time |Volt-Watt response time|10 s |10 s |10 s | |
==== Freq-Watt ==== | ==== Freq-Watt ==== |