manual:module-based:recommended_grid_support_settings

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revision Previous revision
Next revision
Previous revision
manual:module-based:recommended_grid_support_settings [2019/07/07 21:53]
admin [Frequency Ride-through]
manual:module-based:recommended_grid_support_settings [2020/09/16 22:16] (current)
Line 30: Line 30:
   * 4 (+60Hz) for Oahu, Maui, Hawaii   * 4 (+60Hz) for Oahu, Maui, Hawaii
 </WRAP>  | </WRAP>  |
-|Setting -> AC -> Page 6 -> OFR2  time| Over-frequency region trip time, -0.5~-1s later than ride-through until |0.1s, no ride through |+|Setting -> AC -> Page 6 -> OFR2  time| Over-frequency region trip time, -0.5~-1s later than ride-through until |0.1s, no ride through |
 |Setting -> AC -> Page 6 -> OFR1 voltage| Over-frequency region 1 boundary, bias of nominal frequency |3 (+60Hz)  | |Setting -> AC -> Page 6 -> OFR1 voltage| Over-frequency region 1 boundary, bias of nominal frequency |3 (+60Hz)  |
-|Setting -> AC -> Page 6 -> OFR1  time| Over-frequency region trip time, -0.5~-1s later than ride-through until |20 s, making ride-through 19.98 s | +|Setting -> AC -> Page 6 -> OFR1  time| Over-frequency region trip time, -0.5~-1s later than ride-through until |20 s, making ride-through 19.98 s | 
-|Setting -> AC -> Page 6 -> UFR1 voltage| Under-frequency region boundary, bias of nominal frequency|-3 (+60Hz)| +|Setting -> AC -> Page 6 -> UFR1 voltage| Under-frequency region boundary, bias of nominal frequency|-3 (+60Hz)| 
-|Setting -> AC -> Page 6 -> UFR2 voltage| Under-frequency region boundary, bias of nominal frequency|<WRAP>+|Setting -> AC -> Page 6 -> UFR2 voltage| Under-frequency region boundary, bias of nominal frequency|<WRAP>
   * -10 (+60Hz) for Molokai, Lanai   * -10 (+60Hz) for Molokai, Lanai
   * -4 (+60Hz) for Oahu, Maui, Hawaii   * -4 (+60Hz) for Oahu, Maui, Hawaii
Line 85: Line 85:
 ==== Volt-Watt  ==== ==== Volt-Watt  ====
 ^Parameter on HMI (legacy name before M1330)  ^Meaning   ^HECO requirement  ^CA rule 21 requirement  ^IEEE1547 requirement  ^ ^Parameter on HMI (legacy name before M1330)  ^Meaning   ^HECO requirement  ^CA rule 21 requirement  ^IEEE1547 requirement  ^
-|Setting -> AC -> Page 8 -> Volt/Watt V1 |Volt-Watt V1 |1.06 (*480V) |+|Setting -> AC -> Page 8 -> Volt/Watt V1 |Volt-Watt V1 |1.06 (*480V) |1.06 (*480V) |1.06 (*480V) |
 |Setting -> AC -> Page 8 -> Volt/Watt ramp rate |useless, cancelled in V1440 |0 | |Setting -> AC -> Page 8 -> Volt/Watt ramp rate |useless, cancelled in V1440 |0 |
-|Setting -> AC -> Page 8 -> Volt/Watt delay |Volt/Watt return delay |60 s | +|Setting -> AC -> Page 8 -> Volt/Watt delay |Volt/Watt return delay |60 s |60 s |60 s | 
-|Setting -> AC -> Page 8 -> Volt/Watt V2 |Volt-Watt V2 |1.1 (*480V) | +|Setting -> AC -> Page 8 -> Volt/Watt V2 |Volt-Watt V2 |1.1 (*480V) |1.1 (*480V) |1.1 (*480V) | 
-|Setting -> AC -> Page 8 -> Volt/Watt P1 |Volt-Watt P1 |1 (*power setpoint) | +|Setting -> AC -> Page 8 -> Volt/Watt P1 |Volt-Watt P1 |1 (*power setpoint) |1 (*power setpoint) |1 (*power setpoint) | 
-|Setting -> AC -> Page 8 -> Volt/Watt P2 |Volt-Watt P2 |0 (*power setpoint) | +|Setting -> AC -> Page 8 -> Volt/Watt P2 |Volt-Watt P2 |0 (*power setpoint) |0 (*power setpoint) |0 (*power setpoint) | 
-|Setting -> AC -> Page 8 -> Volt/Watt response time |Volt-Watt response time|10 s |+|Setting -> AC -> Page 8 -> Volt/Watt response time |Volt-Watt response time|10 s |10 s |10 s |
  
 ==== Freq-Watt ==== ==== Freq-Watt ====
  • manual/module-based/recommended_grid_support_settings.1562550824.txt.gz
  • Last modified: 2020/09/16 22:07
  • (external edit)