Differences
This shows you the differences between two versions of the page.
Both sides previous revision Previous revision Next revision | Previous revision | ||
manual:module-based:recommended_grid_support_settings [2019/07/07 21:52] admin [Frequency Ride-through] |
manual:module-based:recommended_grid_support_settings [2020/09/16 22:16] (current) |
||
---|---|---|---|
Line 30: | Line 30: | ||
* 4 (+60Hz) for Oahu, Maui, Hawaii | * 4 (+60Hz) for Oahu, Maui, Hawaii | ||
</ | </ | ||
- | |Setting -> AC -> Page 6 -> OFR2 time| Over-frequency region | + | |Setting -> AC -> Page 6 -> OFR2 time| Over-frequency region |
|Setting -> AC -> Page 6 -> OFR1 voltage| Over-frequency region 1 boundary, bias of nominal frequency |3 (+60Hz) | |Setting -> AC -> Page 6 -> OFR1 voltage| Over-frequency region 1 boundary, bias of nominal frequency |3 (+60Hz) | ||
- | |Setting -> AC -> Page 6 -> OFR1 time| Over-frequency region | + | |Setting -> AC -> Page 6 -> OFR1 time| Over-frequency region |
- | |Setting -> AC -> Page 6 -> UFR1 voltage| Under-frequency region | + | |Setting -> AC -> Page 6 -> UFR1 voltage| Under-frequency region |
- | |Setting -> AC -> Page 6 -> UFR2 voltage| Under-frequency region | + | |Setting -> AC -> Page 6 -> UFR2 voltage| Under-frequency region |
* -10 (+60Hz) for Molokai, Lanai | * -10 (+60Hz) for Molokai, Lanai | ||
* -4 (+60Hz) for Oahu, Maui, Hawaii | * -4 (+60Hz) for Oahu, Maui, Hawaii | ||
</ | </ | ||
- | |Setting -> AC -> Page 6 -> UFR1 time |Under-frequency region 1 trip time, -0.5~-1s later than ride-through until |UFR1 time: 20 s, making ride-through 19.98 s| | + | |Setting -> AC -> Page 6 -> UFR1 time |Under-frequency region 1 trip time, -0.5~-1s later than ride-through until |20 s, making ride-through 19.98 s| |
- | |Setting -> AC -> Page 6 -> UFR2 time |Under-frequency region 2 trip time, -0.5~-1s later than ride-through until |UFR2 time: 0.1s, no ride through | | + | |Setting -> AC -> Page 6 -> UFR2 time |Under-frequency region 2 trip time, -0.5~-1s later than ride-through until |0.1s, no ride through | |
|Setting -> AC -> Page 6 -> Restore upper limit freq |Grid reconnect threshold frequency-upper limit, bias of nominal frequency| 0.1 (+60Hz) | | |Setting -> AC -> Page 6 -> Restore upper limit freq |Grid reconnect threshold frequency-upper limit, bias of nominal frequency| 0.1 (+60Hz) | | ||
|Setting -> AC -> Page 6 -> Restore lower limit freq |Grid reconnect threshold frequency-lower limit, bias of nominal frequency| -0.1 (+60Hz) | | |Setting -> AC -> Page 6 -> Restore lower limit freq |Grid reconnect threshold frequency-lower limit, bias of nominal frequency| -0.1 (+60Hz) | | ||
Line 85: | Line 85: | ||
==== Volt-Watt | ==== Volt-Watt | ||
^Parameter on HMI (legacy name before M1330) | ^Parameter on HMI (legacy name before M1330) | ||
- | |Setting -> AC -> Page 8 -> Volt/Watt V1 |Volt-Watt V1 |1.06 (*480V) | | + | |Setting -> AC -> Page 8 -> Volt/Watt V1 |Volt-Watt V1 |1.06 (*480V) |1.06 (*480V) |1.06 (*480V) | |
|Setting -> AC -> Page 8 -> Volt/Watt ramp rate |useless, | |Setting -> AC -> Page 8 -> Volt/Watt ramp rate |useless, | ||
- | |Setting -> AC -> Page 8 -> Volt/Watt delay |Volt/ | + | |Setting -> AC -> Page 8 -> Volt/Watt delay |Volt/ |
- | |Setting -> AC -> Page 8 -> Volt/Watt V2 |Volt-Watt V2 |1.1 (*480V) | | + | |Setting -> AC -> Page 8 -> Volt/Watt V2 |Volt-Watt V2 |1.1 (*480V) |1.1 (*480V) |1.1 (*480V) | |
- | |Setting -> AC -> Page 8 -> Volt/Watt P1 |Volt-Watt P1 |1 (*power setpoint) | | + | |Setting -> AC -> Page 8 -> Volt/Watt P1 |Volt-Watt P1 |1 (*power setpoint) |1 (*power setpoint) |1 (*power setpoint) | |
- | |Setting -> AC -> Page 8 -> Volt/Watt P2 |Volt-Watt P2 |0 (*power setpoint) | | + | |Setting -> AC -> Page 8 -> Volt/Watt P2 |Volt-Watt P2 |0 (*power setpoint) |0 (*power setpoint) |0 (*power setpoint) | |
- | |Setting -> AC -> Page 8 -> Volt/Watt response time |Volt-Watt response time|10 s | | + | |Setting -> AC -> Page 8 -> Volt/Watt response time |Volt-Watt response time|10 s |10 s |10 s | |
==== Freq-Watt ==== | ==== Freq-Watt ==== |