manual:module-based:recommended_grid_support_settings

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revision Previous revision
Next revision
Previous revision
manual:module-based:recommended_grid_support_settings [2019/07/07 21:39]
admin [Enabling]
manual:module-based:recommended_grid_support_settings [2020/09/16 22:16] (current)
Line 26: Line 26:
 ==== Frequency Ride-through ==== ==== Frequency Ride-through ====
 ^Parameter on HMI (legacy name before M1330)  ^Meaning   ^HECO requirement  ^CA rule 21 requirement  ^IEEE1547 requirement  ^ ^Parameter on HMI (legacy name before M1330)  ^Meaning   ^HECO requirement  ^CA rule 21 requirement  ^IEEE1547 requirement  ^
-|Setting -> AC -> Page 6 -> OFR# voltage| Over-frequency region boundary , bias of nominal frequency |OFR1 frequency: 3 (+60Hz)\\  OFR2 frequency:<WRAP>+|Setting -> AC -> Page 6 -> OFR2 voltage| Over-frequency region boundary, bias of nominal frequency |<WRAP>
   * 5 (+60Hz) for Molokai, Lanai     * 5 (+60Hz) for Molokai, Lanai  
   * 4 (+60Hz) for Oahu, Maui, Hawaii   * 4 (+60Hz) for Oahu, Maui, Hawaii
 </WRAP>  | </WRAP>  |
-|Setting -> AC -> Page 6 -> OFR#  time| Over-frequency region trip time, -0.5~-1s later than ride-through until |OFR1 time20 s, making ride-through 19.98 s \\  OFR2 time: 0.1s, no ride through +|Setting -> AC -> Page 6 -> OFR2  time| Over-frequency region trip time, -0.5~-1s later than ride-through until |0.1s, no ride through | 
-|Setting -> AC -> Page 6 -> UFR# voltage| Under-frequency region boundary, bias of nominal frequency| OFR1 frequency: -3 (+60Hz)\\  OFR2 frequency<WRAP>+|Setting -> AC -> Page 6 -> OFR1 voltage| Over-frequency region 1 boundary, bias of nominal frequency |3 (+60Hz) 
 +|Setting -> AC -> Page 6 -> OFR1  time| Over-frequency region 1 trip time, -0.5~-1s later than ride-through until |20 s, making ride-through 19.98 s | 
 +|Setting -> AC -> Page 6 -> UFR1 voltage| Under-frequency region boundary, bias of nominal frequency|-3 (+60Hz)
 +|Setting -> AC -> Page 6 -> UFR2 voltage| Under-frequency region 1 boundary, bias of nominal frequency|<WRAP>
   * -10 (+60Hz) for Molokai, Lanai   * -10 (+60Hz) for Molokai, Lanai
   * -4 (+60Hz) for Oahu, Maui, Hawaii   * -4 (+60Hz) for Oahu, Maui, Hawaii
 </WRAP> | </WRAP> |
-|Setting -> AC -> Page 6 -> UFR# time |Under-frequency region trip time, -0.5~-1s later than ride-through until |UFR1 time: 20 s, making ride-through 19.98 s\\ UFR2 time0.1s, no ride through |+|Setting -> AC -> Page 6 -> UFR1 time |Under-frequency region trip time, -0.5~-1s later than ride-through until |20 s, making ride-through 19.98 s
 +|Setting -> AC -> Page 6 -> UFR2 time |Under-frequency region 2 trip time, -0.5~-1s later than ride-through until |0.1s, no ride through |
 |Setting -> AC -> Page 6 -> Restore upper limit freq |Grid reconnect threshold frequency-upper limit, bias of nominal frequency| 0.1 (+60Hz) | |Setting -> AC -> Page 6 -> Restore upper limit freq |Grid reconnect threshold frequency-upper limit, bias of nominal frequency| 0.1 (+60Hz) |
 |Setting -> AC -> Page 6 -> Restore lower limit freq |Grid reconnect threshold frequency-lower limit, bias of nominal frequency| -0.1 (+60Hz) | |Setting -> AC -> Page 6 -> Restore lower limit freq |Grid reconnect threshold frequency-lower limit, bias of nominal frequency| -0.1 (+60Hz) |
Line 81: Line 85:
 ==== Volt-Watt  ==== ==== Volt-Watt  ====
 ^Parameter on HMI (legacy name before M1330)  ^Meaning   ^HECO requirement  ^CA rule 21 requirement  ^IEEE1547 requirement  ^ ^Parameter on HMI (legacy name before M1330)  ^Meaning   ^HECO requirement  ^CA rule 21 requirement  ^IEEE1547 requirement  ^
-|Setting -> AC -> Page 8 -> Volt/Watt V1 |Volt-Watt V1 |1.06 (*480V) |+|Setting -> AC -> Page 8 -> Volt/Watt V1 |Volt-Watt V1 |1.06 (*480V) |1.06 (*480V) |1.06 (*480V) |
 |Setting -> AC -> Page 8 -> Volt/Watt ramp rate |useless, cancelled in V1440 |0 | |Setting -> AC -> Page 8 -> Volt/Watt ramp rate |useless, cancelled in V1440 |0 |
-|Setting -> AC -> Page 8 -> Volt/Watt delay |Volt/Watt return delay |60 s | +|Setting -> AC -> Page 8 -> Volt/Watt delay |Volt/Watt return delay |60 s |60 s |60 s | 
-|Setting -> AC -> Page 8 -> Volt/Watt V2 |Volt-Watt V2 |1.1 (*480V) | +|Setting -> AC -> Page 8 -> Volt/Watt V2 |Volt-Watt V2 |1.1 (*480V) |1.1 (*480V) |1.1 (*480V) | 
-|Setting -> AC -> Page 8 -> Volt/Watt P1 |Volt-Watt P1 |1 (*power setpoint) | +|Setting -> AC -> Page 8 -> Volt/Watt P1 |Volt-Watt P1 |1 (*power setpoint) |1 (*power setpoint) |1 (*power setpoint) | 
-|Setting -> AC -> Page 8 -> Volt/Watt P2 |Volt-Watt P2 |0 (*power setpoint) | +|Setting -> AC -> Page 8 -> Volt/Watt P2 |Volt-Watt P2 |0 (*power setpoint) |0 (*power setpoint) |0 (*power setpoint) | 
-|Setting -> AC -> Page 8 -> Volt/Watt response time |Volt-Watt response time|10 s |+|Setting -> AC -> Page 8 -> Volt/Watt response time |Volt-Watt response time|10 s |10 s |10 s |
  
 ==== Freq-Watt ==== ==== Freq-Watt ====
  • manual/module-based/recommended_grid_support_settings.1562549986.txt.gz
  • Last modified: 2020/09/16 22:07
  • (external edit)