 ===== Anti-islanding ===== ===== Anti-islanding =====
-^Parameter on HMI (legacy name before M1330)  ^Meaning ^HECO requirement  ^CA rule 21 requirement +^Parameter on HMI (legacy name before M1330)  ^Meaning  ^HECO requirement  ^CA rule 21 requirement  ^IEEE1547 requirement 
-|Setting -> AC -> Page 2 -> Anti-islanding  |to dis-/enable Anti-islanding  |Enabled  |Enabled  |+|Setting -> AC -> Page 2 -> Anti-islanding  |to dis-/enable Anti-islanding  |Enabled  |Enabled  |Enabled  |
 ===== Frequency and Voltage Ride-through ===== ===== Frequency and Voltage Ride-through =====
 ==== Enabling ==== ==== Enabling ====
-^Parameter on HMI (legacy name before M1330)  ^Meaning   ^How to set  ^ +^Parameter on HMI (legacy name before M1330)  ^Meaning   ^HECO requirement  ^CA rule 21 requirement  ^IEEE1547 requirement  ^ 
-|Setting -> AC -> Page 2 -> FVRT enable | to dis-/enable frequency and voltage ride-through |Enabled | +|Setting -> AC -> Page 2 -> FVRT enable | to dis-/enable frequency and voltage ride-through |Enabled |Enabled |Enabled | 
-|Setting -> AC -> Page 2 -> FVRT current limit |to dis-/enable current limiting in ride-through |California: Enabled\\ Other regions: Disabled | +|Setting -> AC -> Page 2 -> FVRT current limit |to dis-/enable current limiting in ride-through |Disabled  |Enabled  |Unknown  |
  
 ==== Frequency Ride-through ==== ==== Frequency Ride-through ====
-^Parameter on HMI (legacy name before M1330)  ^Meaning   ^How to set  ^ +^Parameter on HMI (legacy name before M1330)  ^Meaning   ^HECO requirement  ^CA rule 21 requirement  ^IEEE1547 requirement  ^ 
-|Setting -> AC -> Page 6 -> OFR# voltage| Over-frequency region boundary , bias of nominal frequency |OFR1 frequency: 3 (+60Hz)\\  OFR2 frequency:<WRAP>+|Setting -> AC -> Page 6 -> OFR2 voltage| Over-frequency region boundary, bias of nominal frequency |<WRAP>
   * 5 (+60Hz) for Molokai, Lanai     * 5 (+60Hz) for Molokai, Lanai  
   * 4 (+60Hz) for Oahu, Maui, Hawaii   * 4 (+60Hz) for Oahu, Maui, Hawaii
 </WRAP>  | </WRAP>  |
-|Setting -> AC -> Page 6 -> OFR#  time| Over-frequency region trip time, -0.5~-1s later than ride-through until |OFR1 time20 s, making ride-through 19.98 s \\  OFR2 time: 0.1s, no ride through +|Setting -> AC -> Page 6 -> OFR2  time| Over-frequency region trip time, -0.5~-1s later than ride-through until |0.1s, no ride through | 
-|Setting -> AC -> Page 6 -> UFR# voltage| Under-frequency region boundary, bias of nominal frequency| OFR1 frequency: -3 (+60Hz)\\  OFR2 frequency<WRAP>+|Setting -> AC -> Page 6 -> OFR1 voltage| Over-frequency region 1 boundary, bias of nominal frequency |3 (+60Hz) 
 +|Setting -> AC -> Page 6 -> OFR1  time| Over-frequency region 1 trip time, -0.5~-1s later than ride-through until |20 s, making ride-through 19.98 s | 
 +|Setting -> AC -> Page 6 -> UFR1 voltage| Under-frequency region boundary, bias of nominal frequency|-3 (+60Hz)
 +|Setting -> AC -> Page 6 -> UFR2 voltage| Under-frequency region 1 boundary, bias of nominal frequency|<WRAP>
   * -10 (+60Hz) for Molokai, Lanai   * -10 (+60Hz) for Molokai, Lanai
   * -4 (+60Hz) for Oahu, Maui, Hawaii   * -4 (+60Hz) for Oahu, Maui, Hawaii
 </WRAP> | </WRAP> |
-|Setting -> AC -> Page 6 -> UFR# time |Under-frequency region trip time, -0.5~-1s later than ride-through until |UFR1 time: 20 s, making ride-through 19.98 s\\ UFR2 time0.1s, no ride through |+|Setting -> AC -> Page 6 -> UFR1 time |Under-frequency region trip time, -0.5~-1s later than ride-through until |20 s, making ride-through 19.98 s
 +|Setting -> AC -> Page 6 -> UFR2 time |Under-frequency region 2 trip time, -0.5~-1s later than ride-through until |0.1s, no ride through |
 |Setting -> AC -> Page 6 -> Restore upper limit freq |Grid reconnect threshold frequency-upper limit, bias of nominal frequency| 0.1 (+60Hz) | |Setting -> AC -> Page 6 -> Restore upper limit freq |Grid reconnect threshold frequency-upper limit, bias of nominal frequency| 0.1 (+60Hz) |
 |Setting -> AC -> Page 6 -> Restore lower limit freq |Grid reconnect threshold frequency-lower limit, bias of nominal frequency| -0.1 (+60Hz) | |Setting -> AC -> Page 6 -> Restore lower limit freq |Grid reconnect threshold frequency-lower limit, bias of nominal frequency| -0.1 (+60Hz) |
Line 41: Line 45:
 ==== Voltage Ride-through ==== ==== Voltage Ride-through ====
  
-^Parameter on HMI  (legacy name before M1330) ^Meaning   ^How to set  ^+^Parameter on HMI  (legacy name before M1330) ^Meaning   ^HECO requirement  ^CA rule 21 requirement  ^IEEE1547 requirement  ^
 |Setting -> AC -> Page 5 -> OVR# voltage |Over-voltage region # boundary, ratio of nominal voltage |OVR1 voltage: 1.1 (*480V)\\ OVR2 voltage: 1.2 (*480V) | |Setting -> AC -> Page 5 -> OVR# voltage |Over-voltage region # boundary, ratio of nominal voltage |OVR1 voltage: 1.1 (*480V)\\ OVR2 voltage: 1.2 (*480V) |
 |Setting -> AC -> Page 5 -> OVR# time |Over-voltage region # trip time, 0.02s later than ride-through until |OVR1 time: 0.94 s, making ride-through until 0.92s\\ OVR2 time: 0.1 s, no ride-through | |Setting -> AC -> Page 5 -> OVR# time |Over-voltage region # trip time, 0.02s later than ride-through until |OVR1 time: 0.94 s, making ride-through until 0.92s\\ OVR2 time: 0.1 s, no ride-through |
Line 49: Line 53:
  
 ===== Soft Start Ramp Rate (SS) and Normal Ramp Rate (RR) ===== ===== Soft Start Ramp Rate (SS) and Normal Ramp Rate (RR) =====
-^Parameter on HMI (legacy name before M1330)  ^Meaning   ^How to set  ^+^Parameter on HMI (legacy name before M1330)  ^Meaning   ^HECO requirement  ^CA rule 21 requirement  ^IEEE1547 requirement  ^
 |Setting -> AC -> Page 2 -> P change mode |How the power changes when instructed, step or with ramp |Set to "Ramp rate" to enable SS and RR| |Setting -> AC -> Page 2 -> P change mode |How the power changes when instructed, step or with ramp |Set to "Ramp rate" to enable SS and RR|
 |Setting -> AC -> Page 1 -> Soft-Start reconnection ramp rate |SS |<0.0032 (*Pnom/s)| |Setting -> AC -> Page 1 -> Soft-Start reconnection ramp rate |SS |<0.0032 (*Pnom/s)|
Line 58: Line 62:
 ===== Volt-VAr ===== ===== Volt-VAr =====
  
-^Parameter on HMI (legacy name before M1330)  ^Meaning   ^How to set  ^+^Parameter on HMI (legacy name before M1330)  ^Meaning   ^HECO requirement  ^CA rule 21 requirement  ^IEEE1547 requirement  ^
 |Setting -> AC -> Page 1 -> AC operation mode | to enable Votl-VAr control |Set to V/VAr control to apply Votl-VAr control | |Setting -> AC -> Page 1 -> AC operation mode | to enable Votl-VAr control |Set to V/VAr control to apply Votl-VAr control |
 |Setting -> AC -> Page 7 -> Volt/var point 1 |V1 at Q1, ratio of nominal voltage |0.92 (*480V) | |Setting -> AC -> Page 7 -> Volt/var point 1 |V1 at Q1, ratio of nominal voltage |0.92 (*480V) |
Line 74: Line 78:
 ===== Volt-Watt and Freq-Watt ===== ===== Volt-Watt and Freq-Watt =====
 ==== Enabling  ==== ==== Enabling  ====
-^Parameter on HMI (legacy name before M1330)  ^Meaning   ^How to set  ^+^Parameter on HMI (legacy name before M1330)  ^Meaning   ^HECO requirement  ^CA rule 21 requirement  ^IEEE1547 requirement  ^
 |Setting -> AC -> Page 2 -> Active power regulation |Set to Volt control to apply Volt-Watt |Unaware of present CPUC/HECO politics | |Setting -> AC -> Page 2 -> Active power regulation |Set to Volt control to apply Volt-Watt |Unaware of present CPUC/HECO politics |
 |Setting -> AC -> Page 2 -> Active power regulation |Set to Freq control to apply Freq-Watt |Unaware of present CPUC/HECO politics | |Setting -> AC -> Page 2 -> Active power regulation |Set to Freq control to apply Freq-Watt |Unaware of present CPUC/HECO politics |
Line 80: Line 84:
  
 ==== Volt-Watt  ==== ==== Volt-Watt  ====
-^Parameter on HMI (legacy name before M1330)  ^Meaning   ^How to set  ^ +^Parameter on HMI (legacy name before M1330)  ^Meaning   ^HECO requirement  ^CA rule 21 requirement  ^IEEE1547 requirement  ^ 
-|Setting -> AC -> Page 8 -> Volt/Watt V1 |Volt-Watt V1 |1.06 (*480V) |+|Setting -> AC -> Page 8 -> Volt/Watt V1 |Volt-Watt V1 |1.06 (*480V) |1.06 (*480V) |1.06 (*480V) |
 |Setting -> AC -> Page 8 -> Volt/Watt ramp rate |useless, cancelled in V1440 |0 | |Setting -> AC -> Page 8 -> Volt/Watt ramp rate |useless, cancelled in V1440 |0 |
-|Setting -> AC -> Page 8 -> Volt/Watt delay |Volt/Watt return delay |60 s | +|Setting -> AC -> Page 8 -> Volt/Watt delay |Volt/Watt return delay |60 s |60 s |60 s | 
-|Setting -> AC -> Page 8 -> Volt/Watt V2 |Volt-Watt V2 |1.1 (*480V) | +|Setting -> AC -> Page 8 -> Volt/Watt V2 |Volt-Watt V2 |1.1 (*480V) |1.1 (*480V) |1.1 (*480V) | 
-|Setting -> AC -> Page 8 -> Volt/Watt P1 |Volt-Watt P1 |1 (*power setpoint) | +|Setting -> AC -> Page 8 -> Volt/Watt P1 |Volt-Watt P1 |1 (*power setpoint) |1 (*power setpoint) |1 (*power setpoint) | 
-|Setting -> AC -> Page 8 -> Volt/Watt P2 |Volt-Watt P2 |0 (*power setpoint) | +|Setting -> AC -> Page 8 -> Volt/Watt P2 |Volt-Watt P2 |0 (*power setpoint) |0 (*power setpoint) |0 (*power setpoint) | 
-|Setting -> AC -> Page 8 -> Volt/Watt response time |Volt-Watt response time|10 s |+|Setting -> AC -> Page 8 -> Volt/Watt response time |Volt-Watt response time|10 s |10 s |10 s |
  
 ==== Freq-Watt ==== ==== Freq-Watt ====
-^Parameter on HMI (legacy name before M1330)  ^Meaning   ^How to set  ^+^Parameter on HMI (legacy name before M1330)  ^Meaning   ^HECO requirement  ^CA rule 21 requirement  ^IEEE1547 requirement  ^
 |Setting -> AC -> Page 8 -> Freq/Watt point |Fstart, the frequency Freq-Watt supposed to start |0.25 (+60Hz) | |Setting -> AC -> Page 8 -> Freq/Watt point |Fstart, the frequency Freq-Watt supposed to start |0.25 (+60Hz) |
 |Setting -> AC -> Page 8 -> Freq/Watt ramp rate |Freq-Watt slope |0.05 (*power setpoint/Hz) | |Setting -> AC -> Page 8 -> Freq/Watt ramp rate |Freq-Watt slope |0.05 (*power setpoint/Hz) |