====== Recommended grid-support settings ====== | ====== Recommended grid-support settings ====== | ||
+ | |||
+ | ===== Scope ===== | ||
+ | This instruction guides how to set the grid-support functions required by | ||
+ | * HECO Rule 14H | ||
+ | * CPUC Rule 21 | ||
+ | * IEEE 1547 | ||
+ | |||
+ | This document covers the following models | ||
+ | * PWS1-50K-NA | ||
+ | * PWS1-100K-NA | ||
+ | * PWS1-150K-NA | ||
+ | * PWS1-250K-NA | ||
+ | * PWS1-500KTL-NA | ||
+ | |||
===== Anti-islanding ===== | ===== Anti-islanding ===== | ||
- | ^ | + | ^Parameter on HMI (legacy name before M1330) |
- | |Setting -> AC -> Page 2| Anti-islanding| to dis-/enable Anti-islanding | Set to Enabled | | + | |Setting -> AC -> Page 2 -> Anti-islanding |
===== Frequency and Voltage Ride-through ===== | ===== Frequency and Voltage Ride-through ===== | ||
==== Enabling ==== | ==== Enabling ==== | ||
- | ^ | + | ^Parameter on HMI (legacy name before M1330) |
- | |Setting -> AC -> Page 2 |FVRT enable | to dis-/enable frequency and voltage ride-through |Set to Enabled | | + | |Setting -> AC -> Page 2 -> FVRT enable | to dis-/enable frequency and voltage ride-through |Enabled |Enabled |Enabled | |
- | |Setting -> AC -> Page 2 |FVRT current limit |to dis-/enable current limiting in ride-through |California: Enabled\\ Other regions: | + | |Setting -> AC -> Page 2 -> FVRT current limit |to dis-/enable current limiting in ride-through |Disabled |
==== Frequency Ride-through ==== | ==== Frequency Ride-through ==== | ||
- | ^ | + | ^Parameter on HMI (legacy name before M1330) |
- | |Setting -> AC -> Page 6| OFR# voltage| Over-frequency region | + | |Setting -> AC -> Page 6 -> OFR2 voltage| Over-frequency region |
* 5 (+60Hz) for Molokai, Lanai | * 5 (+60Hz) for Molokai, Lanai | ||
* 4 (+60Hz) for Oahu, Maui, Hawaii | * 4 (+60Hz) for Oahu, Maui, Hawaii | ||
</ | </ | ||
- | |Setting -> AC -> Page 6| OFR# time| Over-frequency region | + | |Setting -> AC -> Page 6 -> OFR2 time| Over-frequency region |
- | |Setting -> AC -> Page 6| UFR# voltage| Under-frequency region | + | |Setting -> AC -> Page 6 -> OFR1 voltage| Over-frequency region 1 boundary, bias of nominal frequency |3 (+60Hz) |
+ | |Setting -> AC -> Page 6 -> OFR1 | ||
+ | |Setting -> AC -> Page 6 -> UFR1 voltage| Under-frequency region | ||
+ | |Setting -> AC -> Page 6 -> UFR2 voltage| Under-frequency | ||
* -10 (+60Hz) for Molokai, Lanai | * -10 (+60Hz) for Molokai, Lanai | ||
* -4 (+60Hz) for Oahu, Maui, Hawaii | * -4 (+60Hz) for Oahu, Maui, Hawaii | ||
</ | </ | ||
- | |Setting -> AC -> Page 6| UFR# time |Under-frequency region | + | |Setting -> AC -> Page 6 -> UFR1 time |Under-frequency region |
- | |Setting -> AC -> Page 6| Restore upper limit freq |Grid reconnect threshold frequency-upper limit, bias of nominal frequency| 0.1 (+60Hz) | | + | |Setting -> AC -> Page 6 -> UFR2 time |Under-frequency region 2 trip time, -0.5~-1s later than ride-through until |0.1s, no ride through | |
- | |Setting -> AC -> Page 6| Restore lower limit freq |Grid reconnect threshold frequency-lower limit, bias of nominal frequency| -0.1 (+60Hz) | | + | |Setting -> AC -> Page 6 -> Restore upper limit freq |Grid reconnect threshold frequency-upper limit, bias of nominal frequency| 0.1 (+60Hz) | |
+ | |Setting -> AC -> Page 6 -> Restore lower limit freq |Grid reconnect threshold frequency-lower limit, bias of nominal frequency| -0.1 (+60Hz) | | ||
==== Voltage Ride-through ==== | ==== Voltage Ride-through ==== | ||
- | ^ | + | ^Parameter on HMI |
- | |Setting -> AC -> Page 5|OVR# voltage |Over-voltage region # boundary, ratio of nominal voltage |OVR1 voltage: 1.1 (*480V)\\ OVR2 voltage: 1.2 (*480V) | | + | |Setting -> AC -> Page 5 -> OVR# voltage |Over-voltage region # boundary, ratio of nominal voltage |OVR1 voltage: 1.1 (*480V)\\ OVR2 voltage: 1.2 (*480V) | |
- | |Setting -> AC -> Page 5|OVR# time |Over-voltage region # trip time, 0.02s later than ride-through until |OVR1 time: 0.94 s, making ride-through until 0.92s\\ OVR2 time: 0.1 s, no ride-through | | + | |Setting -> AC -> Page 5 -> OVR# time |Over-voltage region # trip time, 0.02s later than ride-through until |OVR1 time: 0.94 s, making ride-through until 0.92s\\ OVR2 time: 0.1 s, no ride-through | |
- | |Setting -> AC -> Page 5|UVR# voltage |Under-voltage region # boundary, ratio of nominal voltage |UVR1 voltage: 0.88 (*480V)\\ | + | |Setting -> AC -> Page 5 -> UVR# voltage |Under-voltage region # boundary, ratio of nominal voltage |UVR1 voltage: 0.88 (*480V)\\ |
- | |Setting -> AC -> Page 5|UVR# time |Under-voltage region # trip time, 0.02s later than ride-through until |UVR1 time: 20 s, making ride-through until 19.98s\\ UVR2 time: 11 s, making ride-through until 10.98s\\ UVR3 time: 0.1 s, no ride-through | | + | |Setting -> AC -> Page 5 -> UVR# time |Under-voltage region # trip time, 0.02s later than ride-through until |UVR1 time: 20 s, making ride-through until 19.98s\\ UVR2 time: 11 s, making ride-through until 10.98s\\ UVR3 time: 0.1 s, no ride-through | |
===== Soft Start Ramp Rate (SS) and Normal Ramp Rate (RR) ===== | ===== Soft Start Ramp Rate (SS) and Normal Ramp Rate (RR) ===== | ||
+ | ^Parameter on HMI (legacy name before M1330) | ||
+ | |Setting -> AC -> Page 2 -> P change mode |How the power changes when instructed, step or with ramp |Set to "Ramp rate" to enable SS and RR| | ||
+ | |Setting -> AC -> Page 1 -> Soft-Start reconnection ramp rate |SS |< | ||
+ | |Setting -> AC -> Page 1 -> Grid reconnection delay |Grid reconnection delay |300 s| | ||
+ | |Setting -> AC -> Page 1 -> Normal Ramp Rate |RR |1 (*Pnom/s)| | ||
+ | |||
===== Volt-VAr ===== | ===== Volt-VAr ===== | ||
- | ^ | + | ^Parameter on HMI (legacy name before M1330) |
- | |Setting -> AC -> Page 1| AC operation mode | to enable Votl-VAr control |Set to V/VAr control to apply Votl-VAr control | | + | |Setting -> AC -> Page 1 -> AC operation mode | to enable Votl-VAr control |Set to V/VAr control to apply Votl-VAr control | |
- | |Setting -> AC -> Page 7| Volt/var point 1 |V1 at Q1, ratio of nominal voltage |0.92 (*480V) | | + | |Setting -> AC -> Page 7 -> Volt/var point 1 |V1 at Q1, ratio of nominal voltage |0.92 (*480V) | |
- | |Setting -> AC -> Page 7| Volt/var point 2 |V2 at Q2, ratio of nominal voltage |0.97 (*480V) | | + | |Setting -> AC -> Page 7 -> Volt/var point 2 |V2 at Q2, ratio of nominal voltage |0.97 (*480V) | |
- | |Setting -> AC -> Page 7| Volt/var point 3 |V3 at Q3, ratio of nominal voltage |1.03 (*480V) | | + | |Setting -> AC -> Page 7 -> Volt/var point 3 |V3 at Q3, ratio of nominal voltage |1.03 (*480V) | |
- | |Setting -> AC -> Page 7| Volt/var point 4 |V4 at Q4, ratio of nominal voltage |1.07 (*480V) | | + | |Setting -> AC -> Page 7 -> Volt/var point 4 |V4 at Q4, ratio of nominal voltage |1.07 (*480V) | |
- | |Setting -> AC -> Page 7| Max. inductive reactive regulation |Q4, ratio of nominal capacity |0.3 (*Pnom) | | + | |Setting -> AC -> Page 7 -> Max. inductive reactive regulation |Q4, ratio of nominal capacity |0.3 (*Pnom) | |
- | |Setting -> AC -> Page 7| Max. capacitive reactive regulation |Q1, ratio of nominal capacity |0.3 (*Pnom) | | + | |Setting -> AC -> Page 7 -> Max. capacitive reactive regulation |Q1, ratio of nominal capacity |0.3 (*Pnom) | |
- | |Setting -> AC -> Page 7| Initial. inductive reactive regulation 3 |Q3, ratio of nominal capacity |0 (*Pnom) | | + | |Setting -> AC -> Page 7 -> Initial. inductive reactive regulation 3 |Q3, ratio of nominal capacity |0 (*Pnom) | |
- | |Setting -> AC -> Page 7| Initial. capacitive reactive regulation 2 |Q2, ratio of nominal capacity |0 (*Pnom) | | + | |Setting -> AC -> Page 7 -> Initial. capacitive reactive regulation 2 |Q2, ratio of nominal capacity |0 (*Pnom) | |
- | |Setting -> AC -> Page 7| Volt/var reaction time |Volt-VAr response time |1 s | | + | |Setting -> AC -> Page 7 -> Volt/var reaction time |Volt-VAr response time |1 s | |
- | |Setting -> AC -> Page 7| Volt/var Vref |Vref, ratio of nominal voltage |1 (*480V)| | + | |Setting -> AC -> Page 7 -> Volt/var Vref |Vref, ratio of nominal voltage |1 (*480V)| |
===== Volt-Watt and Freq-Watt ===== | ===== Volt-Watt and Freq-Watt ===== | ||
==== Enabling | ==== Enabling | ||
- | ^ | + | ^Parameter on HMI (legacy name before M1330) |
- | |Setting -> AC -> Page 2 |Active power regulation |Set to Volt control to apply Volt-Watt |Unaware of present CPUC/HECO politics | | + | |Setting -> AC -> Page 2 -> Active power regulation |Set to Volt control to apply Volt-Watt |Unaware of present CPUC/HECO politics | |
- | |Setting -> AC -> Page 2 |Active power regulation |Set to Freq control to apply Freq-Watt |Unaware of present CPUC/HECO politics | | + | |Setting -> AC -> Page 2 -> Active power regulation |Set to Freq control to apply Freq-Watt |Unaware of present CPUC/HECO politics | |
- | |Setting -> AC -> Page 2 |Active power regulation |Set to V/F control to apply Volt-Watt and Freq-Watt at the same time. Yet Freq-Watt prior to Volt-Watt |Unaware of present CPUC/HECO politics | | + | |Setting -> AC -> Page 2 -> Active power regulation |Set to V/F control to apply Volt-Watt and Freq-Watt at the same time. Yet Freq-Watt prior to Volt-Watt |Unaware of present CPUC/HECO politics | |
==== Volt-Watt | ==== Volt-Watt | ||
- | ^ | + | ^Parameter on HMI (legacy name before M1330) |
- | |Setting -> AC -> Page 8 |Volt/Watt V1 |Volt-Watt V1 |1.06 (*480V) | | + | |Setting -> AC -> Page 8 -> Volt/Watt V1 |Volt-Watt V1 |1.06 (*480V) |1.06 (*480V) |1.06 (*480V) | |
- | |Setting -> AC -> Page 8 |Volt/Watt ramp rate |useless, | + | |Setting -> AC -> Page 8 -> Volt/Watt ramp rate |useless, |
- | |Setting -> AC -> Page 8 |Volt/Watt delay |Volt/ | + | |Setting -> AC -> Page 8 -> Volt/Watt delay |Volt/ |
- | |Setting -> AC -> Page 8 |Volt/Watt V2 |Volt-Watt V2 |1.1 (*480V) | | + | |Setting -> AC -> Page 8 -> Volt/Watt V2 |Volt-Watt V2 |1.1 (*480V) |1.1 (*480V) |1.1 (*480V) | |
- | |Setting -> AC -> Page 8 |Volt/Watt P1 |Volt-Watt P1 |1 (*power setpoint) | | + | |Setting -> AC -> Page 8 -> Volt/Watt P1 |Volt-Watt P1 |1 (*power setpoint) |1 (*power setpoint) |1 (*power setpoint) | |
- | |Setting -> AC -> Page 8 |Volt/Watt P2 |Volt-Watt P2 |0 (*power setpoint) | | + | |Setting -> AC -> Page 8 -> Volt/Watt P2 |Volt-Watt P2 |0 (*power setpoint) |0 (*power setpoint) |0 (*power setpoint) | |
- | |Setting -> AC -> Page 8 |Volt/Watt response time |Volt-Watt response time|10 s | | + | |Setting -> AC -> Page 8 -> Volt/Watt response time |Volt-Watt response time|10 s |10 s |10 s | |
==== Freq-Watt ==== | ==== Freq-Watt ==== | ||
- | ^ | + | ^Parameter on HMI (legacy name before M1330) |
- | |Setting -> AC -> Page 8 |Freq/Watt point |Fstart, | + | |Setting -> AC -> Page 8 -> Freq/Watt point |Fstart, |
- | |Setting -> AC -> Page 8 |Freq/Watt ramp rate |Freq-Watt slope |0.05 (*power setpoint/ | + | |Setting -> AC -> Page 8 -> Freq/Watt ramp rate |Freq-Watt slope |0.05 (*power setpoint/ |
- | |Setting -> AC -> Page 8 |Freq-Watt response time |Freq-Watt response time |0.50 s | | + | |Setting -> AC -> Page 8 -> Freq-Watt response time |Freq-Watt response time |0.50 s | |