 Sinexcel PCS supports DC dispatch and AC dispatch Sinexcel PCS supports DC dispatch and AC dispatch
 ===== What is DC dispatch and AC dispatch ===== ===== What is DC dispatch and AC dispatch =====
-inverter is a bi-port network, it has two ports, DC and AC. In theory, the AC power equals to DC power, if there's no self consumption.+An inverter is a bi-port network, it has two ports, DC and AC. In theory, the AC power equals to DC power, if there's no self consumption.
  
-But actually, there is efficiency issue. We have the following equtions+But actually, there is an efficiency issue. We have the following equtions
  
 In Charging In Charging
Line 21: Line 21:
  
 You can You can
-  * designate AC active power (total, but not each string for multi-string version)+  * designate AC active power (total, but NOT each string for multi-string version)
   * designate AC reactive power    * designate AC reactive power 
-  * activate P-PF, Volt-VAr, Freq-Watt, Volt-Watt+  * activate PF-P, Volt-VAr, Freq-Watt, Volt-Watt
 You can NOT You can NOT
   * designate DC power   * designate DC power
-  * nor designate DC current+  * designate DC current
  
 ===== String dispatch===== ===== String dispatch=====
Line 36: Line 36:
   * designate AC active power** of each string for multi-string version**, but NOT total power   * designate AC active power** of each string for multi-string version**, but NOT total power
   * designate AC reactive power in total  (total, but not each string for multi-string version)   * designate AC reactive power in total  (total, but not each string for multi-string version)
-  * activate P-PF, Volt-VAr, Freq-Watt, Volt-Watt+  * activate PF-P, Volt-VAr, Freq-Watt, Volt-Watt
 You can NOT You can NOT
   * designate DC power   * designate DC power
Line 45: Line 45:
  
 You can You can
-  * designate DC power but not DC current (of each string for PWS-500KTL multi-string version) +  * designate DC power but not DC current (of each string for multi-string version) 
-  * or designate DC current but not DC power (of each string for PWS-500KTL multi-string version)+  * or designate DC current but not DC power (of each string for multi-string version)
  
 You can NOT You can NOT
   * designate AC active power   * designate AC active power
   * designate AC reactive power   * designate AC reactive power
-  * activate P-PF, Volt-VAr, Freq-Watt, Volt-Watt+  * activate PF-P, Volt-VAr, Freq-Watt, Volt-Watt
  