how_to:dc_dispatch_and_ac_dispatch

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revision Previous revision
Next revision
Previous revision
how_to:dc_dispatch_and_ac_dispatch [2019/05/20 03:19]
admin [DC dispatch]
how_to:dc_dispatch_and_ac_dispatch [2020/09/16 21:42] (current)
Line 2: Line 2:
 Sinexcel PCS supports DC dispatch and AC dispatch Sinexcel PCS supports DC dispatch and AC dispatch
 ===== What is DC dispatch and AC dispatch ===== ===== What is DC dispatch and AC dispatch =====
-inverter is a bi-port network, it has two ports, DC and AC. In theory, the AC power equals to DC power, if there's no self consumption.+An inverter is a bi-port network, it has two ports, DC and AC. In theory, the AC power equals to DC power, if there's no self consumption.
  
-But actually, there is efficiency issue. We have the following equtions+But actually, there is an efficiency issue. We have the following equtions
  
 In Charging In Charging
Line 19: Line 19:
  
 In AC dispatch mode,  In AC dispatch mode, 
 +
 You can You can
-  * designate AC active power +  * designate AC active power (total, but NOT each string for multi-string version) 
-  * designate AC reactive power +  * designate AC reactive power  
-  * activate P-PF, Volt-VAr, Freq-Watt, Volt-Watt+  * activate PF-P, Volt-VAr, Freq-Watt, Volt-Watt
 You can NOT You can NOT
- * designate DC power +  * designate DC power 
- nor designate DC current+  * designate DC current
  
 +===== String dispatch=====
 +
 +
 +String dispatch mode is kind of AC dispatching for multi-string PCS,
 + 
 +You can
 +  * designate AC active power** of each string for multi-string version**, but NOT total power
 +  * designate AC reactive power in total  (total, but not each string for multi-string version)
 +  * activate PF-P, Volt-VAr, Freq-Watt, Volt-Watt
 +You can NOT
 +  * designate DC power
 +  * nor designate DC current
 ===== DC dispatch===== ===== DC dispatch=====
  
 In DC dispatch mode,  In DC dispatch mode, 
 +
 You can You can
-  * designate DC power but not DC current (of each string for PWS-500KTL multi-string version) +  * designate DC power but not DC current (of each string for multi-string version) 
-  * or designate DC current but not DC power (of each string for PWS-500KTL multi-string version)+  * or designate DC current but not DC power (of each string for multi-string version)
  
 You can NOT You can NOT
   * designate AC active power   * designate AC active power
   * designate AC reactive power   * designate AC reactive power
-  * activate P-PF, Volt-VAr, Freq-Watt, Volt-Watt+  * activate PF-P, Volt-VAr, Freq-Watt, Volt-Watt
  