Differences
This shows you the differences between two versions of the page.
Next revision | Previous revision | ||
how_to:dc_dispatch_and_ac_dispatch [2019/05/20 02:24] admin created |
how_to:dc_dispatch_and_ac_dispatch [2020/09/16 21:42] (current) |
||
---|---|---|---|
Line 1: | Line 1: | ||
====== Select DC dispatch or AC dispatch ====== | ====== Select DC dispatch or AC dispatch ====== | ||
Sinexcel PCS supports DC dispatch and AC dispatch | Sinexcel PCS supports DC dispatch and AC dispatch | ||
- | | + | ===== What is DC dispatch and AC dispatch ===== |
- | * AC dispatch | + | An inverter is a bi-port network, it has two ports, DC and AC. In theory, the AC power equals to DC power, if there' |
+ | |||
+ | But actually, there is an efficiency issue. We have the following equtions | ||
+ | |||
+ | In Charging | ||
+ | $$P_{DC}=P_{AC}\times \eta _{charge}$$ | ||
+ | In Discharging | ||
+ | $$P_{AC}=P_{DC}\times \eta _{discharge}$$ | ||
+ | |||
+ | Once one of $P_{DC}$ and $P_{AC}$ is designated, the other one is determined. | ||
+ | |||
+ | Depending on the designated port, there is AC dispatching mode and DC dispatching mode | ||
+ | |||
+ | ===== AC dispatch===== | ||
+ | |||
+ | |||
+ | In AC dispatch mode, | ||
+ | |||
+ | You can | ||
+ | | ||
+ | * designate AC reactive power | ||
+ | * activate PF-P, Volt-VAr, Freq-Watt, Volt-Watt | ||
+ | You can NOT | ||
+ | * designate | ||
+ | * designate DC current | ||
+ | |||
+ | ===== String | ||
+ | |||
+ | |||
+ | String dispatch mode is kind of AC dispatching for multi-string PCS, | ||
+ | |||
+ | You can | ||
+ | * designate | ||
+ | * designate AC reactive power in total (total, but not each string for multi-string version) | ||
+ | * activate PF-P, Volt-VAr, Freq-Watt, Volt-Watt | ||
+ | You can NOT | ||
+ | * designate DC power | ||
+ | * nor designate DC current | ||
+ | ===== DC dispatch===== | ||
+ | |||
+ | In DC dispatch mode, | ||
+ | |||
+ | You can | ||
+ | * designate DC power but not DC current (of each string for multi-string version) | ||
+ | * or designate DC current but not DC power (of each string for multi-string version) | ||
+ | |||
+ | You can NOT | ||
+ | * designate AC active power | ||
+ | * designate AC reactive power | ||
+ | * activate PF-P, Volt-VAr, Freq-Watt, Volt-Watt |