definition:battery_dis-_charge_sequence [2019/07/01 21:14] admin |
definition:battery_dis-_charge_sequence [2020/09/16 21:41] (current) |
||
---|---|---|---|
Line 20: | Line 20: | ||
Example 2. The battery voltage is 600V in initial, the maximum charging current (Max charging current) is 100A, the requested charging power (Target active power) is 50kW, the PWS2-30K will charge in 50kW, because the charging DC current is just $50kW\div 600V=83A$, and as the voltage rises, such as 660V, the power is still 50kW, because the charging DC current is $50kW\div 660V=76A$. But if 670V is the constant voltage charging threshold set by user, when the voltage reaches 670V, the power will reduce gradually till 0. | Example 2. The battery voltage is 600V in initial, the maximum charging current (Max charging current) is 100A, the requested charging power (Target active power) is 50kW, the PWS2-30K will charge in 50kW, because the charging DC current is just $50kW\div 600V=83A$, and as the voltage rises, such as 660V, the power is still 50kW, because the charging DC current is $50kW\div 660V=76A$. But if 670V is the constant voltage charging threshold set by user, when the voltage reaches 670V, the power will reduce gradually till 0. | ||
- | ===== float charge voltage ===== | + | ===== Float charge voltage ===== |
The float charge is **ONLY for lead-acid or lead-carbon battery**. For lead batteries, the float charging voltage shall be a little lower than slow charge voltage (topping charge mode), and there is a threshold called " | The float charge is **ONLY for lead-acid or lead-carbon battery**. For lead batteries, the float charging voltage shall be a little lower than slow charge voltage (topping charge mode), and there is a threshold called " |