====== Fault Current Contribution ====== | ====== Fault Current Contribution ====== | ||
- | |||
Sinexcel has received inquiries as to the relationship of fault current contributed and kilo-Amperes Interrupting Capacity (kAIC) ratings. | Sinexcel has received inquiries as to the relationship of fault current contributed and kilo-Amperes Interrupting Capacity (kAIC) ratings. | ||
- | With regard to the fault current contribution of Sinexcel inverters, the contribution from the microinverters | + | With regard to the fault current contribution of Sinexcel inverters, the contribution from the inverters |
Only circuit breakers, fuses, and some load-rated switches have AIC ratings. As a current source, a utility interactive inverter does not, by itself, require an AIC rating. | Only circuit breakers, fuses, and some load-rated switches have AIC ratings. As a current source, a utility interactive inverter does not, by itself, require an AIC rating. |